The steam cylinder is disposable and must be replaced at the end of the cylinder's life. Cylinder life
will vary according to water supply conditions and humidifier usage.
WARNING
!
Risk of humidifier canister meltdown, smoke and fire. Can cause fire suppression system
activation, fire and smoke alarm activation, serious equipment and building damage, injury
and death.
Using a humidifier canister that has reached the end of it's service life can be extremely
hazardous. If the canister cannot be replaced immediately at the end of life condition, turn Off
the power and water supply to the humidifier and remove the canister until a replacement
canister can be installed.
Table 61
Humidifier canister part numbers
200V, 208V, 230V
Unit Model
DS 028-042
DS 053-105
Removing the Old Canister
To replace a used-up humidifier cylinder, refer to Figure 103 and perform these steps:
1. Turn off the water supply to unit.
2. The old cylinder must be drained completely before removing. This is done by pushing the auto
on/off/drain switch to the Drain position.
3. When completely drained, push the auto on/off/drain switch to the Off position.
4. Open the main electrical disconnect during the entire cylinder change operation.
5. The power wires to the cylinder are attached by cylinder plugs to the electrode pins on top of the
cylinder. Pull up to remove the plugs from the pins.
6. Use slotted screwdriver to loosen the steam hose clamp(s)
7. Disconnect the steam hose by pulling it straight up.
8. Loosen reversible cylinder zip tie.
9. The cylinder is now ready to be lifted out of the unit.

Figure 103Removing the old canister

380/415V, 460V, 575V
163814P1
163814P4
163814P1
163814P2
Humidifier Model
MES 10
MES 20
139
Maintenance