Figure 16 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all
compressor models
Condenser Cleanout Access
33"
(838mm)
35"
(889mm)
Alternate Refrigerant
Piping Entrance
High Volt Connection(s)
1-1/2"
(38mm)
76"
(1930mm)
2"
(51mm)
Table 13
Weights for upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Compressor Type
Semi-Hermetic
GLYCOOL/Dual-Cool
Scroll or Digital Scroll
TOP VIEW
86" (2184mm)
85" (2159mm)
FRONT VIEW
Dry Weight, lb (kg) approximate
Model
028-042
Water/Glycol
1980 (898)
2130 (966)
Water/Glycol
1830 (830)
GLYCOOL/Dual-Cool
1980 (898)
Note: Front air return unit shown. For rear
return unit, in addition to front service area
shown, also include 25" (635mm) on one side
of unit for access to rear return filter box.
See DPN001196, Figure 30
3/4" (19mm)
Bezels
Low Volt Connection(s)
Shaded area indicates a
recommended minimum
clearance for component
access.
21
Liebert DS Dimensions and Weights
Required for
condenser cleanout
Minimum required
for blower replacement
34"
(864mm)
DPN001164
Rev. 1
24"
(610mm)