Important Safety Instructions; Save These Instructions - Emerson Liebert DS Series User Manual

Table of Contents

Advertisement

I
S
MPORTANT
AFETY

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions that should be followed during the installation
and maintenance of the Liebert DS
operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in
this manual. Follow all operating and user instructions.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect local and remote power supplies before working within.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included
and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM microprocessor does not isolate power from the unit, even in the "unit off"
mode. Some internal components require and receive power even during the "unit off" mode of
Liebert iCOM control.
The factory-supplied optional disconnect switch is inside the unit. The line side of this switch
contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote
disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
WARNING
!
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.
This unit contains fluids and gases under high pressure. Relieve pressure before working with
piping.
WARNING
!
Risk of refrigerant system rupture or explosion from overpressurization. Can cause
equipment damage, injury or death.
For systems requiring EU CE compliance (50Hz), the system installer must provide and
install a discharge pressure relief valve rated for a maximum of 500 psig (34bar) in the high
side refrigerant circuit. Do not install a shutoff valve between the compressor and the field
installed relief valve. The pressure relief valve must be CE-certified to the EU Pressure
Equipment Directive by an EU "Notified Body."
WARNING
!
Risk of contact with high-speed moving parts. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit.
Do not operate unit with any or all cabinet panels removed. Do not operate upflow units
without installing a plenum, ductwork or guard over the blower opening(s) on the top surface
of the unit cabinet.
Ductwork must be connected to the blower(s), or a plenum must be installed on the blower
deck for protection from rotating blower wheel(s) on upflow units.
I
NSTRUCTIONS
. Read this manual thoroughly before attempting to install or
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents