Figure 51 Component Dimensions-Downflow, Water/Glycol/Glycool, 105Kw (30 Ton), Forward-Curved And Ec Fan, All Compressor Models; Forward-Curved And Ec Fan; Table 37 Component Weights-Downflow, Water/Glycol/Glycool, 105Kw (30 Ton), All Compressor; Models; Forward-Curved And Ec Fan - Emerson Liebert DS Series User Manual

Table of Contents

Advertisement

Figure 51 Component dimensions—downflow, water/glycol/GLYCOOL, 105kW (30 ton), forward-curved
and EC fan, all compressor models; forward-curved and EC fan
Compressor Assembly
76"
(1930mm)
33"
(838mm)
Table 37
Component weights—downflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor

models; forward-curved and EC fan

Component
Compressor Assembly
Filter & Electric Box Assembly
Blower & Coil Assembly,
Forward-Curve Fan / EC Fan)
Drawing views are simplified
with panels removed to show
overall dimensions.
See disassembly and handling
instructions in installation manual.
26"
(660mm)
Assembled Length
Dry Weight, Approximate, Including Panels, lb (kg)
Semi-Hermetic Compressor
Water/Glycol
GLYCOOL/Dual-Cool
1320 (600)
270 (123)
1820 (827) /
1560 (708)
Disassembling the Liebert DS for Transport
Filter & Electric
Box Assembly
Blower and
Coil Assembly
105" (2667mm)
131" (3327mm)
Water/Glycol
1320 (600)
1200 (545)
270 (123)
270 (123)
2180 (991) /
1820 (827) /
1915 (870)
1560 (708)
63
39"
(991mm)
41-11/16"
(1059mm)
76"
(1930mm)
Assembled
Height
59-7/16"
(1510mm)
37"
(940mm)
DPN001060
Rev. 1
Scroll Compressor
GLYCOOL/Dual-Cool
1200 (545)
270 (123)
2180 (991) /
1915 (870)