Figure 96 Primary connection locations—upflow, water/glycol/GLYCOOL, 105kW (30 ton), all
NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is ± 1/2" (13mm).
3. Field routed alternatives for water/glycol
connections.
4. See submittal page DPN001192 for
blower outlet and deck dimensional data.
6"
(152mm)
17-3/16"
(437mm)
3-7/8"
(98mm)
14-1/4"
(362mm)
15-7/8"
(403mm)
LEFT SIDE SECTION VIEW OF UNIT
Table 58
Piping data—upflow, upflow, water/glycol/GLYCOOL, 105kW (30 ton), all
Point
Description
W1
Water/Glycol/GLYCOOL Access (Bottom)
3
W2
Water/Glycol/GLYCOOL Access (Top)
3
W3
Water/Glycol/GLYCOOL Access (Side)
3
WS
Water/Glycol/GLYCOOL Supply
3
WR
Water/Glycol/GLYCOOL Return
3
CGD*
Condensate Gravity Drain
CPD
Condensate Pump Discharge (Opt)
HUM
Humidifier Supply Line
ECS
Econ-O-Coil Supply
ECR
Econ-O-Coil Return
E1
Electrical Conn. (High Volt)
E2
Electrical Conn. (High Volt)
LV1
Electrical Conn. (Low Volt)
LV2
Electrical Conn. (Low Volt)
LV3
Electrical Conn. (Low Volt)
LV4
Electrical Conn. (Low Volt)
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do not
trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all
local codes.
8"
35"
(203mm)
(889mm)
2-7/8"
(73mm)
3-1/2"
(89mm)
W3
WS
WR
CGD*
Blower
Outlet
(3353mm)
TOP VIEW OF UNIT
CGD*
FRONT SECTION VIEW OF UNIT
(Left Front Panel Not Shown)
X
inches (mm)
inches (mm)
126-1/8 (3204)
126-1/8 (3204)
-
-
-
-
102-3/8 (2600)
13-5/8 (346)
101-1/8 (2569)
13-1/8 (333)
101-1/8 (2569)
10-1/4 (260)
101-1/8 (2569)
5-1/4 (133)
98-1/2 (2502)
30 (762)
93 (2362)
30 (762)
41-1/8 (1045)
30-3/8 (772)
38-7/8 (987)
30-3/8 (772)
35-1/8 (892)
30-3/8 (772)
31-5/8 (803)
30-3/8 (772)
123
Piping Schematics
All dimensions from
rear corner of unit
including panels
Blower
Blower
Outlet
Outlet
LV1
LV3
LV2
LV4
132"
Front Of Unit
Y
Connection Size /
Opening, inches (mm)
9 (229)
3-1/2 x 8 (89 x 203)
9 (229)
3-1/2 x 8 (89 x 203)
-
6 x 17-3/16 (152 x 437)
-
2-1/8 Cu Sweat
-
2-1/8 Cu Sweat
-
3/4 FPT
1/2 Cu Sweat
1/4 Cu Sweat
2-5/8 Cu Sweat
2-5/8 Cu Sweat
2-1/2
2-1/2
DPN001258
Rev. 0
7/8
7/8
7/8
7/8