Installation Manual
| DCIPS1B-S-00-B6 Power Supply System
Battery
Breaker Size
[A]
Wire Size
[mm
/AWG]
2
4.5.6 Symmetry Connection
1. Attach the interblock connection plates between the batteries.
2. Insert a suitably sized cable lug into one pole of the interblock connection plate. Fasten
the lugs and plates to individual battery poles.
3. For 2-block battery symmetry measurement fix one wire of the symmetry cable to the
cable lug in the mid-point of the battery string, see Figure 4-11.
4. For 4-block measurement fix the 3 wires (red, green and blue) of the symmetry cable
to individual cable lugs. Colour coding of the cables must be respected for proper
symmetry measurement see Figure 4-12.
Figure 4-11 2-block Symmetry Measurement (for illustration only)
Figure 4-12 4-Block Symmetry Measurement (for illustration only)
26
40A
50A
65A
10/6
10/6
16/4
Table 4-3 Cable Sizes
+1 (208) 635-6400 | www.transtector.com
NOTE The interblock Connection Kit is not delivered with the system.
NOTE Symmetry cable is normally pre-connected to the system, see Figure 4-7.
4.5.7 Temperature Sensor Connection
Temperature Sensor Connection for supervising battery temperature is usually delivered
pre-installed when used. On the occasion that it is fitted later it is connected using the three-
pin plug according to the same procedure as for the alarm connections.
The sensor itself should be fastened to the battery after battery installation: Unwind the
cable, remove the paper covering the adhesive for the sensor and fasten the sensor to the
battery as shown in Figure 4-13.
Temp. Sensor
Figure 4-13 Temperature Sensor Connection
NOTE Temperature sensor is normally pre connected to the system, see Figure
4-7.
+1 (208) 635-6400 | www.transtector.com
27