Installation Manual
| DCIPS1B-S-00-B6 Power Supply System
4.5 Rear Connections
All cable connections for the DCIPS1B system are available at the rear of the system, see
Figure 4-3.
CAUTION Use UL-listed wires with an insulation rating to at least 90°C.
WARNING Before inserting the cable into the connector, remove as little insulation on the
cable as possible, to prevent the stranded conductor to come loose and touch any other
conductive parts.
LOAD
BATTERY
CONNECTIONS
CONNECTIONS
X9
X10
X6
SIGNAL
CONNECTIONS
Figure 4-3 Rear Connections
SIGNAL
4.5.1 DC Earth Connection (FRAME GROUND)
CONNECTIONS
WARNING The power system needs to be properly grounded to the rack or cabinet frame
to ensure its safe and efficient operation.
The Earth Connection (Frame Ground) of the rack is located on the rear as shown in Figure
4-3.
To connect:
1. Loosen the screw (M5).
2. Attach suitably sized cable lug.
3. Tighten the screw with torque 3.5Nm.
Recommended cable size is 6 mm
Figure 4-4 DC Earth Connections
20
LOAD
BATTERY
GMT CONFIGURATION
CONNECTIONS
CONNECTIONS
CONNECTIONS
X5
RS485
FRAME
GROUND
1-phase
2 x 1-phase
X9
X10
X6
.
2
+1 (208) 635-6400 | www.transtector.com
4.5.2 Mains Connection
GMT CONFIGURATION
The DCIPS1B system family is available with two options for mains connection:
First, check which mains solution is delivered and then follow the appropriate installation
AC
instructions below.
Connectors are situated on the right rear side of the system (Figure 4-3), labeled and
configured as seen in Figure 4-5.
X5
FRAME
GROUND
+1 (208) 635-6400 | www.transtector.com
WARNING Ensure that mains input is turned off before connecting. The grounding
must be connected to PE terminal as first.
CAUTION Depending on deployment region with regards to lightning strikes and
heavy inductive energy, it is highly recommended to install AC Surge Protection
Class C.
•
Single-phase / Phase to Phase (USA) connection
•
2x Single-phase / Phase to Phase (USA) connection
CONNECTIONS
RS485
1-phase
2 x 1-phase
Figure 4-5 Mains Connection (viewed from rear)
Shelf Type
Number of
(See product label)
Rectifiers
Single-phase
2
AC Input
2 x Single-phase
2
AC Input
Table 4-1 Recommended Mains Circuit Protection
AC
Imax at
Recommended
100 VAC
Mains CB
18.6 A
C32A
at 100VAC
9.3 A
2 x C32A
at 100VAC
21