Installation Warning; Electrical And Fire Enclosure - Infinite Transtector DCIPS1B-S-00-B6 Installation Manual

Power supply system
Table of Contents

Advertisement

Installation Manual
| DCIPS1B-S-00-B6 Power Supply System

3.1.3 Installation Warning

The following safety guidelines should be observed when transporting or moving the system:
Before moving the Power System, read the system specifications sheet to determine
whether the install site meets all the size, environmental, and power requirements.
The system and the equipment included, should only be moved and installed by
qualified personnel to prevent bodily injury or any other hazardous conditions.
3.1.4 Restricted Access Area Warnings
The Power System is designed for installation in locations with restricted access often
secured by a locking mechanism. It can therefore be accessed only by a trained service
person, who is fully aware of the restrictions applied to the location, or by an authority
responsible for the location.

3.1.5 Electrical and Fire Enclosure

The unit is for building-in. A suitable Electrical and Fire enclosure shall be provided.
3.1.6 System Enclosure
Appropriate measures need to be taken to avoid intrusion of any unwanted objects or insects
into conductive areas of the power system as there is a potential risk of system damage.
Disclaimer: TRANSTECTOR assumes no liability or responsibility for system failures
resulting from inappropriate enclosure around the system.
3.1.7 Operating Temperature Warnings
To prevent the Power System from overheating, an automatic shutdown mechanism has
been installed. It is not recommended to continually operate the Power System in an area
that exceeds the maximum recommended operating temperature.
3.1.8 Electrical Safety Warnings
The following are electrical safety recommendations for working near the Power System:
WARNING Observe low voltage safety precautions before attempting to work on the
system when power is connected. Potentially lethal voltages are present within the system.
WARNING Caution must be exercised when handling system power cables. Damage to
the insulation or contact points of cables can cause contact with lethal voltages. For safety
reasons, cables should be connected to the power system before power is applied.
14
+1 (208) 635-6400 | www.transtector.com
+1 (208) 635-6400 | www.transtector.com
Remove all metallic jewelry like watches or rings that may present a hazard while
working on the power system.
Before connecting the AC input source to the power system, always verify voltage.
Verify the AC source capacity. See system specifications for AC information.
All AC connections must conform to local codes and regulations, e.g. ANSI, CEC,
NEC, etc.
When making AC connections, all AC power and DC load distribution breakers should
be in the OFF position.
All circuit breakers should meet the original design specifications of the system. In
addition, equipment connected to the system should not overload the circuit breakers
as this may have a negative effect on overcurrent protection and supply wiring,
causing system or user harm.
Verify the DC capacity before making connections. See system specifications for DC
information.
Potentially lethal voltages are present within the system. Ensure that all power supplies
are completely isolated by turning all power switches OFF, disconnecting all relevant
connectors and removing all relevant breakers before attempting any maintenance
work. Do not rely on switches alone to isolate the power supply. Batteries should
also be disconnected.
Potentially lethal voltages are present within this system. Ensure that low voltage
safety requirements are implemented before attempting to work on the system with
power connected.
Potentially lethal voltages can be induced if the equipment is not grounded (earthed)
correctly. Ensure that all ground connections are secure.
3.1.9 Grounding
WARNING Grounding connection must be performed before operating the system. Refer
to local codes, e.g. ANSI, CEC, NEC, T1-333, ETSI 300-386-TC specifying the connection
of power system to building ground. In case of any doubt regarding the grounding
connection, please contact a person responsible for the system.
WARNING The system should be hard-wired to the incoming earth ground. A solid high
current ground connection capable of sinking the maximum system current is required.
3.1.10 Batteries
WARNING When installing or replacing batteries, there is risk of explosion if an incorrect
battery type is used.
15

Advertisement

Table of Contents
loading

Table of Contents