Figure 7-1 Unlocking The Controller; Figure 7-2 Removing The Controller; Controller Replacement - Infinite Transtector DCIPS1B-S-00-B6 Installation Manual

Power supply system
Table of Contents

Advertisement

Installation Manual
| DCIPS1B-S-00-B6 Power Supply System
Fault
Possible Cause
Symmetry Fault Battery at end of life.
Wrong symmetry cable connection.
Wrongly set Symmetry limit value.
Low Battery
Battery temperature drops below the
Temperature
set Low battery temperature limit.
high Battery
Battery temperature exceeded the set
Temperature
limit.
Temp. Probe
The temperature probe is not properly
Failure
connected to the system.
Faulty temperature probe.
Temperature probe wire is
interrupted.
Temperature difference between the
controller temperature and the probe
temperature is greater than 60°C.
Alarms Blocked
Alarm is manually activated by the
serviceman on the site (used during
(only with LCD
display)
system servicing, no other alarm is
displayed)
If none of the above solves the problem please contact customer support.
To phone us please visit www.transtector.com.
36
Suggestion/Solution
Verify the battery condition.
Verify the symmetry cable
connection.
Verify the Symmetry limit value.
Check the heating of the system.
Check the ambient temperature
(it should not be lower than
recommended battery temperature).
Check the cooling or ventilation.
Verify the battery condition.
Check the Battery Current Limit.
Verify the temperature probe
connection.
Verify the internal / external
temperature via controller front panel.
Replace the faulty probe with a new
one.
Identify the root cause of the hot
environment at the batteries and/or
controller.
Needs to be manually turned OFF to
allow the alarms to be displayed
+1 (208) 635-6400 | www.transtector.com

7.1 Controller Replacement

A faulty Controller can be easily replaced with a new one:
1. Loosen the front screw in the top left corner of the controller front panel using a flat
screwdriver, see Figure 7-1.

Figure 7-1 Unlocking the Controller

2. Pull the controller out of the shelf as shown in Figure 7-2.

Figure 7-2 Removing the Controller

3. Reverse the process to insert the new controller into the empty slot and fasten the screw.
CAUTION
After controller start-up, verify if the appropriate configuration file is uploaded
to the controller. If necessary refer to the
+1 (208) 635-6400 | www.transtector.com
Chapter 7 Replacing Modules
PowCom™ User
Guide.
37