Appendix B - Csa Certificate Extract - Infinite Transtector DCIPS1B-S-00-B6 Installation Manual

Power supply system
Table of Contents

Advertisement

Installation Manual
| DCIPS1B-S-00-B6 Power Supply System
ELECTRICAL RATING
Input Type
V
Single Phase (High Power)
100 - 240
Two Phase (High Power)
100 - 240
Single Phase (Low Power)
100 - 240
Two Phase (Low Power)
100 - 240
*Maximum output current is derated to:
25 A from 100-180 Vac and 23 A from 90-100 Vac at 47°C, 55°C ambient
21 A from 90 to 264 Vac at 75°C ambient
45 A from 180 Vac to 264 Vac at 55°C ambient
CONDITIONS OF ACCEPTABILITY
1. The shelves are to be installed only by trained service personnel, according to manufacturer installation
instructions.
2. Evaluated as Class I (earthed equipment). Reliable earth connection shall be provided in the end use
installation.
3. Evaluated for use in a Pollution Degree 2 environment, up to 3048 m altitude.
4. Temperature tests shall be considered for specific installation conditions in the end system.
5. Suitable fire enclosure shall be provided in the end system.
6. All secondary output circuits for all models are SELV.
7. The shelves shall be properly bonded to the main protective earthing termination in the end product.
8. The input connectors for all models are suitable for field connection.
9. These products are intended to be installed within equipment that is for use in a RESTRICTED ACCESS
LOCATION (RAL) and the end-product instructions shall so state.
10. Consideration shall be given to the Output Terminals, that they do not exceed 85°C at the maximum
operating ambient temperature.
11. These products are provided with component power supplies which are double-poled/neutral fused and
marked per 2.7.6, which is visible after installation of power supplies. However, additional marking may
be necessary based on installation of these products and should be considered during the end-product
evaluation.
12. Consideration should also be given to re-conducting Temperature Tests if the equipment is intended for
use in an ambient other than 47, 55 and 75°C .
13. Load breakers maximum load must not exceed the below limits:
14. 25 to 30 A circuit breaker rating- Maximum load per breaker must not exceed 18 A at 47 and 55°C
ambient and not exceed 7.5 A at 75°C ambient 1 to 20 A circuit breaker rating- Maximum load per
breaker must not exceed 80% of breaker current rating at 47 and 55°C ambient and not exceed 30% of
breaker current rating at 75°C ambient.
42

Appendix B - CSA Certificate Extract

Input, AC
Maximum Output, DC
A (max)
V (dc)
Hz
A
16-11
50 - 60
46 - 57
52*
8-5.5
50 - 60
46 - 57
52*
(Per phase)
9-4
50 - 60
46 - 57
15
4.5-2
50 - 60
46 - 57
15
(Per phase)
+1 (208) 635-6400 | www.transtector.com
About Transtector Systems:
Transtector Systems, an Infinite Electronics brand, leads the industry with a comprehensive product portfolio
and specialized expertise in consulting, design and manufacturing of AC, DC, data and signal surge protection,
communications power cabinets, and EMP protection.
Transtector provides valuable end-to-end power and signal integrity solutions for markets that include
telecommunications, medical imaging, transportation, energy, security and the military. Our goal is to support the urgent
surge-protection requirements of our customers with responsive customer service, technical support and a wide-range of
quality AC, DC and data line surge protection products in-stock and available for same-day shipping.
Contact us at +1 208 635 6400 or online at www.transtector.com.
About Infinite Electronics:
Infinite Electronics is a leading global supplier of electronic components serving the urgent needs of engineers through
a family of highly recognized and trusted brands. Our portfolio brands are specialists within their respective product set,
offering broad inventories of engineering-grade product, paired with expert technical support and same day shipping.
Over 100,000 customers across a diverse set of markets rely upon Infinite Electronics to stock and reliably ship urgently
needed products every day.
+1 (208) 635-6400 | www.transtector.com
43

Advertisement

Table of Contents
loading

Table of Contents