System Components; System Controller - Infinite Transtector DCIPS1B-S-00-B6 Installation Manual

Power supply system
Table of Contents

Advertisement

Installation Manual
| DCIPS1B-S-00-B6 Power Supply System
RECTIFIER MODEL
Efficiency
Input Current (max)
Output Current (max)
53.5V float
Output Power
Operating Temperature
(without derating)
Input Voltage
(Nominal 100-240VAC)
Output Voltage
Load sharing
Dimensions (WxHxD)
Weight
Cooling
Fan-cooled, speed and alarm controlled, air flow direction rear to front
Protection
Short circuit proof, automatic current limiting, selective shutdown of modules at
Alarms
High output voltage/ shutdown, Low voltage/ module failure
LED Indication
Green:
Yellow:
Red:
Audible noise
MECHANICAL
Dimensions (WxHxD)
480 mm x 44.45 mm x 266 mm
Weight of the system
6.5 kg
(fully equipped)
Mounting Options
19"/ ETSI / Mid-mount
Cable Entry
Rear Access
STANDARD COMPLIANCE / ENVIRONMENTAL
EMC and Immunity
ETSI EN 300 386 V.1.5
EN 55022
EN 55024, EN 61000-4
Safety
EN 60950-1
Operating Temperature
-40°C to +75°C, derating over +47°C (see appendix B)
Storage Temperature
-40°C to +85°C
10
DCIPS1B-1200
95% typical @ I
nom
out
<7.3A
22.4A
1200W @ >180VAC
750W @ 90-180VAC
55°C
90-300VAC
46-57VDC
< 5% of nominal current
40.6 (1.6") x 101.62(4") x 228.5(9") mm
1.1 kg
excessive output voltage.
Power ON
Current limit/ thermal protection
Fan failure / Over temperature
Pre-warning / thermal protection
Communication Failure (flashing)
Module failure / high output voltage shutdown
<55dBA according to ISO7779
+1 (208) 635-6400 | www.transtector.com

2.4 System Components

The DCIPS1B system is delivered with all components mounted according to the ordered
configuration. The main components are described below and in later chapters of the
manual.
There are 2 versions of DCIPS1B shelf available depending on the value of battery current
shunt used: 20 A or 80 A.
CAUTION Low Power Shelf version (20 A version) provides better resolution for battery
current reading and it is suitable for low power applications with maximum battery charge
current less than 5A.

2.4.1 System Controller

The DCIPS1B power system can be controlled by the ACX Advanced controller. The
description and operation of this controller is covered in a separate manual which
isavailable at:
www.transtector.com
2.4.2 DC Distribution
DC Distribution consists of maximum 1 battery and 4 load breakers available in a variety
of sizes.
The distribution unit is designed for switching the battery and load on and off.
The battery and load breakers are supervised by measuring the voltage drop across
each breaker. In the case of load breakers, those which are not connected to any load
will not cause a breaker alarm even if they are left open.
A battery fuse alarm is generated after the battery voltage drops below a certain level,
depending on the actual battery capacity and condition.
Low Voltage Disconnect (LVD)
The system is equipped with a low voltage battery disconnect which prevents the
batteries from deep discharging, thus prolonging the battery life. The disconnect requires
a detected mains failure at the supervision unit (controller).
If disconnection occurs, the batteries will not supply power to the load until they have
been recharged to a set voltage level, which can be adjusted by the user.
If disconnection occurs, the batteries will be reconnected when the mains supply returns.
+1 (208) 635-6400 | www.transtector.com
11