System Parameters; Figure 2-3 Power System With Extended Rear And Top Cover Kit; Figure 2-4 Power System With Rear And Top Cover Kit - Infinite Transtector DCIPS2B-S-00-B11 Installation Manual

Power supply system
Table of Contents

Advertisement

Installation Manual
| DCIPS2B-S-00-B11 Power Supply System
To meet the requirements of different application, there are two kinds of Rear and Top Cover
Kit available:
Rear and Top Cover Kit for cabinets
Extended Rear and Top Cover Kit for open relay racks.
Top Cover
AC Input Cover
AC Cable Entry
DC Cable Entry
Extended Rear Cover

Figure 2-3 Power System With Extended Rear and Top Cover Kit

NOTE The cable entry on the rear of the shelf is factory supplied and opened. If you want
to route the cables from the bottom or side, remove the knockouts. For AC cable entry,
you have to install the supplied PG21.
Top Cover
AC Cable Entry

Figure 2-4 Power System with Rear and Top Cover Kit

NOTE The Rear and Top Cover Kit and Extended Rear and Top Cover Kit are optional
components and just provided according to your order.
10
Rear Cover
+1 (208) 635-6400 | www.transtector.com
+1 (208) 635-6400 | www.transtector.com

2.2 System Parameters

OUTPUT
Power (max)
5.4kW load + 3.5kW battery charge @ 230/400VAC nominal
8.7kW load + 1.9kW battery charge @ 120VAC nominal
Output Current (max)
100A load + 65A battery charge @ 230/400VAC nominal
70A load + 35A battery charge @ 120VAC nominal
Voltage
44-57.6VDC
INPUT
Voltage Range
100-120VAC, 1W+N+PE, 50/60Hz
200-240VAC, 2W+PE, 50/60Hz
208-240/360-416VAC, 3W+N+PE, 50/60Hz
Frequency
47-63Hz
Input Current
1-phase 50A @ 100-120VAC, 39A @ 200-240VAC
3-phase 13A per phase @ 230/400VAC
Power factor
>0.98
Surge Protection
Optional
DC DISTRIBUTION & BATTERY MANAGEMENT
Battery Breakers
1 or 3 x 80A, 100A or 125A
Symmetry Inputs
Up to 6
Programmable LVD / PLD
125A (voltage) / 125A (voltage/time)
Load Breakers
5 x 18mm / 6 x 13mm, depending on number of battery breakers.
Ratings
single pole - 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
(see datasheet for details)
two pole - 80A, 100A; three pole - 125A, 150A
MONITORING AND CONTROL
Controller
PCC or ACX Advanced
Local Interface
4 x 20' LCD, 4-key menu, USB (ACX only) and RS232
Remote Interface
Ethernet / Modem using PowCom™ software
Visual Indication
Green LED - System On
Yellow LED - Message(s)
Red LED - Alarm(s)
Analog Inputs
12 x voltage inputs (range 0-100VDC) - 6 max. for symmetry
Alarm Outputs
4 x potential free relays (C, NC, NO)
Digital Inputs
2 x, Logic 0: U<10VDC, Logic 1: U>12VDC (ACX only)
Digital Outputs
2 x, open collector type (ACX only)
Temperature measurement
2 x Temperature probe (Battery, Ambient)
CONNECTIONS
Battery connections
M8 lugs, +Ve common from bus bar
AC connections
Max. 7AWG/10mm
2
, screw type connector
Load breaker connections
-Ve termination direct to breakers, +Ve common from busbar
11AWG/4mm²
Alarm connections
Max. 14AWG/1.5mm², screw type connector
11