Menu no. /
Description
1.01
Pressure setpoint
Value range: 0.1 ... 16.0 bar*
Factory setting: 4.0 bar
1.04
Activation threshold of the pump
(in % from default value in 1.01)
Value range: 50 ... 99 %
Factory setting: 90 %
1.05
Deactivation threshold of the pump
(in % from default value in 1.01)
Value range: 101 ... 130 %
Factory setting: 115 %
1.06
Pump switch-off time delay
Value range: 10 ... 300 s
Factory setting: 180 s
1.10
Activation delay, peak-load pump
Value range: 1 ... 10 s
Factory setting: 1 s
2.01
ModBus approval
Values: off, on
Factory setting: off
2.02
ModBus: Baud rate
Values: 9600; 19200; 38400; 76800
Factory setting: 19200
2.03
ModBus: Slave address
Value range: 1 ... 254
Factory setting: 10
Installation and operating instructions Wilo-Control EC-Fire
Menu 1.00: Control parameters
Menu 2.00: Communication parameters (Modbus)