Kampmann UniLine 10 Assembly And Installation Instructions Manual

Kampmann UniLine 10 Assembly And Installation Instructions Manual

Cassette

Advertisement

Quick Links

Cassette UniLine
Assembly and Installation Instructions
Keep these instructions in a safe place for future use!
Kampmann.de/installation_manuals
I164 11/20 GB SAP-Nr. 1021206

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UniLine 10 and is the answer not in the manual?

Questions and answers

Summary of Contents for Kampmann UniLine 10

  • Page 1 Cassette UniLine Assembly and Installation Instructions Keep these instructions in a safe place for future use! Kampmann.de/installation_manuals I164 11/20 GB SAP-Nr. 1021206...
  • Page 2 Kampmann GmbH & Co. KG Kampmann UK Ltd. Friedrich-Ebert-Str. 128 - 130 Dial House, Govett Avenue 49811 Lingen (Ems) Shepperton, Middlesex, TW17 8AG Germany Great Britain +49 591 7108-660 +44 (0)1932 228592 +49 591 7108-173 +44 (0)1932 228949 export@kampmann.de info@kampmann.co.uk...
  • Page 3: Table Of Contents

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Table of Contents About these instructions Key to symbols Intended use Safety information 2.1 Limits of operation and use Transport and storage Scope of delivery Installation 5.1 Installation dimensions for Cassette UniLine 5.2 Installation points and LPHW connection...
  • Page 4 Allgemeines | Informationen zu dieser Anleitung Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.5.2.1 Function keys, display elements 10.5.2.2 Operation 10.6 Alarm messages 10.7 Troubleshooting A11 – A17 10.8 Cabling 10.8.1 General information 10.8.2 KaController 10.8.3 External room temperature sensor 10.8.4 Inputs for processing external contacts (e.g.
  • Page 5: About These Instructions

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains General | About these instructions, Key to symbols About these instructions Carefully read these instructions in full prior to any assembly and installation work! Anyone involved with the installation, commissioning and use of this...
  • Page 6: Intended Use

    Intended use | Applications, Specialist knowledge Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Intended use Kampmann UniLine door air curtains are produced in compliance with the state of the art and recognised safety regulations. Nevertheless their use can result in danger to people or damage to the unit or other material property if they are not properly installed or properly used.
  • Page 7: Safety Information

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Safety information | Hazards, responsibility Safety information Only allow a qualified electrician to perform installation, assembly and maintenance work on electrical units in compliance with VDE guidelines. Wiring should comply with the applicable VDE regulations and provisions laid down by the regional electricity providers.
  • Page 8: Limits Of Operation And Use

    Limits of operation and use Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 2.1 Limits of operation and use Limits of operation Min./max. water temperature °C 40 - 90 Min./max. air intake temperature °C 6 - 40 Min./max.
  • Page 9: Transport And Storage

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Transport and storage, Delivery, Installation Transport and storage Please note all applicable safety and accident prevention regulations. Attention! Risk of sharp edges! Wear gloves, safety shoes and suitable protective clothing during transportation! Two people are needed to carry the unit.
  • Page 10: Installation Dimensions For Cassette Uniline

    Installation | UniLine model 10 - 25 with wall brackets Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 5.1 Installation dimensions of Cassette UniLine View from below Cross-section (enlarged) Front view Side view Fixing points Outlet air rectifier Perforated plate with filter Flow 3/4"...
  • Page 11: Installation Points And Lphw Connection

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Installation | UniLine model 30 with wall brackets 5.2 Fixing points and LPHW connection Top view Side view, LPHW connection side Isometric view Isometric view Side view, electrical connection side...
  • Page 12: Hydraulic Connections

    Hydraulic connections | UniLine door air curtains Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Hydraulic Sonnections Safety information Connecting up the hydraulics requires expertise in heating engineering. Note the following guidelines for integrating the system before starting work on the unit or on the control: Maximum temperature of heating medium 90 °C.
  • Page 13 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Hydraulic connections | UniLine door air curtains 6.1 Installation of the thermoelectric shut-off valve and outlet air temperature limiting valve Flow with air vent Return with air vent Outlet temperature limit valve, type 100967; installation in the...
  • Page 14: Installation Of Remote Sensor For Outlet Air Temperature Limit Valve

    Hydraulic connections | UniLine door air curtains Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 6.2 Installation of remote sensor for outlet air temperature limit valve Proceed as follows when installing the remote sensor: Open the service hatch (1) on the left side of...
  • Page 15: Technical Data

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Technical data | Models Technical data Unit Cassette UniLine AC Model Length 1035 1535 2035 2535 Weight Current consumption 1.82 2.67 3.70 4.75 Max. electrical power consumption [W] Mains voltage...
  • Page 16: Commissioning

    Commissioning | Checks, switching-on, permanent decommissioning Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Commissioning Pre-commissioning checks: Is the unit fitted to the ceiling with the appropriate fixing brackets? Electrical connection: Is all cabling in accordance with the applicable ambient regulations?
  • Page 17: Maintenance

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Maintenance | Filters, fans and heat exchanger Maintenance Fans and heat exchanger Caution! Read the safety information in these instructions before working on the fans and heat exchangers! Maintain the maintenance intervals prescribed by legislation. Interim maintenance depends on the general conditions on site.
  • Page 18: Electrical Wiring

    Electrical wiring | Safety Information, electrical wiring Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring Safety information The electrical wiring of this product requires expert knowledge in the field of electrical engineering. This knowledge, generally learned in vocational training in one of the fields stated, is not described separately here.
  • Page 19: Uniline Ac, Electromechanical Model (*00)

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine AC, electromechanical model (*00) Control options Cabling and wiring depend on the control accessories used. The relevant wiring diagrams are supplied with the units. 10.1 UniLine AC, electromechanical model (*00)
  • Page 20 Electrical wiring | UniLine AC, electromechanical model (*00) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains UniLine AC electrical installation Operation of single UniLine AC door air curtain Example: 5-stage summer-winter switch surface-mounted, type 100928 UniLine AC...
  • Page 21: Uniline Ac, Model For On-Site Control (*P)

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine AC, model for on-site control (*P) 10.2 UniLine AC, model for on-site control (*P) Description of switches The mains voltage is wired to the voltage supply terminals on the door air curtain.
  • Page 22 Electrical wiring | UniLine AC, model for on-site control (*P) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains...
  • Page 23: Uniline Ec, Electromechanical Model With Internal Fault Signal Processing (*00)

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, electromechanical model with internal fault signal processing (*00) 10.3 UniLine EC, electromechanical model with internal fault signal processing (*00) Description of switches The mains voltage is wired to the voltage supply terminals on the door...
  • Page 24 Electrical wiring | UniLine EC, electromechanical model Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains with internal fault signal processing (*00)
  • Page 25 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, electromechanical model with internal fault signal processing (*00)
  • Page 26: Uniline Ec, Electromechanical Model With External Fault Signal Processing (*T)

    Electrical wiring | UniLine EC, electromechanical model Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains with external fault signalling (*T) 10.4 UniLine EC, electromechanical model with external fault signal (*T) Feed line Control signal Description of switches:...
  • Page 27 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, electromechanical model with external fault message (*T)
  • Page 28 Electrical wiring | UniLine EC, electromechanical model Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains with external fault signalling (*T)
  • Page 29: Uniline Ec, Kacontrol Version (*C1)

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.5 UniLine EC, KaControl version (*C1) 10.5.1 Intended use Kampmann KaControllers and KaControl modules are built in line with the state of the art and recognised safety regulations. Nevertheless, their use...
  • Page 30: Operation Of The Kacontroller

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.5.2 KaController operation The KaController is capable of controlling the wide range of Kampmann systems. KaControllers are equipped with state of the art technology and offer users the option of adapting the air conditioning of buildings to individual needs.
  • Page 31: Function Keys, Display Elements

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.5.2.1 Function keys, display elements Display with LED background lighting ON/OFF key (depending on setting) - ON / OFF (factory setting)
  • Page 32: Operation

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.5.2.2 Operation The KaController is operated by the navigator dial and the function keys. The functions that can be called up and set using the navigator are identical on both versions (with and without function keys at the side).
  • Page 33 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) Switching control off and on When the control is switched on, the display shows the default view with the current room temperature setpoint and the fan stage set.
  • Page 34 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Fan setting Press the FAN key (quick access) or use the navigator dial to call up the "Fan setting" selection menu.
  • Page 35 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) Summer mode/winter mode adjustment Press the MODE key (quick access) or use the navigator dial to call up the "Operating modes" selection menu.
  • Page 36 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Time setting Press the TIMER key (quick access) 1x or use the navigator dial to call up the "Time setting" selection menu.
  • Page 37 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) Time switch programs The KaController provides the option of programming switching on and off times using a timer program if rooms are only to be air conditioned during certain times of the day.
  • Page 38 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Press the TIMER key twice (quick access) or use the navigator dial to call up the "Timer programs" selection menu. Use the navigator dial to call up the "Timer programs" menu.
  • Page 39 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) Step 4: Set the switching-off time you require by turning the navigator dial. Once the minutes have been set, press the navigator dial to apply the switching-off time and to call up the timer program start screen.
  • Page 40 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Deleting all timer programs and the time Perform the following steps to delete all timer programs and the time: 1. Switch off the KaController by:...
  • Page 41: Alarm Messages

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.6 Alarm messages The KaController displays faults by means of the alarm messages listed in the table below. The alarm messages are displayed according to their priority.
  • Page 42 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.7 KaController installation Installation/Dismantling Electrical wiring Connect the KaController to the nearest KaControl in accordance with the wiring diagram. The maximum bus length between the KaController and the KaControl is 30 m.
  • Page 43: Troubleshooting

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.7.1 Troubleshooting A11 – A17 Faults in the motor of a slave unit are not shown on the KaController. Only a motor fault in a master unit is shown on the KaController.
  • Page 44 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains A14 Condensation alarm The condensation alarm of a unit is shown on the KaController by the display "A14". A unit with an active condensation alarm automatically closes all valves.
  • Page 45: Cabling

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.8 Cabling 10.8.1 General information Route all low voltage cables along the shortest route. Ensure that low-voltage and high-voltage cables are separated, using metal partitions in cable ducts.
  • Page 46: External Room Temperature Sensor

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.8.3 External room temperature sensor ** Route shielded, paired All KaControl master units have an analogue input to connect an cables, e.g. CAT5 external room temperature sensor.
  • Page 47: Addressing - Single-Circuit Controls

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.9 Addressing – Single-circuit controls KaControl units in single-circuit controls with a maximum of 6 units need not be addressed. Define the master unit/slave unit by connecting the KaController.
  • Page 48: Setting The Unit Configuration By Means Of Dip Switches

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.10 Setting the unit configuration by means of DIP switches Set the configuration of a KaControl unit using the DIP switch on the PCB.
  • Page 49 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) DIP switch no. 1 DIP switch no. 1 must be set to ON to actuate a KaControl by means of 0…10 V signals within a building management system provided by others.
  • Page 50: Parameter Settings

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.11 Parameter settings Special system requirements can be configured using parameter settings in the Service menu. Special system requirements may include:...
  • Page 51: Parameter Settings

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.12. Parameter settings 10.12.1 Setting of absolute setpoint temperature or ± 3K Parameter P36 It may be necessary in office or hotel applications for the system operator to specify a base setpoint.
  • Page 52: On/Off, Eco/Day Functions

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.12.2 ON/OFF, Eco/Day functions Parameter P38 The ON/OFF key function and the timer programs are specified using parameter P38. Use the ON/OFF button and the timer programs to switch the unit ON and OFF or between Eco and Day mode.
  • Page 53: Di2 Function

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.12.3 DI2 function The digital input DI1 is predominantly used to execute specific functions. If the use of the digital input DI2 is needed, then the following settings must be made: 1.
  • Page 54: Function Of Digital Outputs V1 And V2

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.12.4 Function of digital outputs V1 and V2 The function of the digital output V1 is permanently assigned. The function of the digital output V2 can be configured using parameters.
  • Page 55: Function Of Multifunctional Inputs Ai1, Ai2 And Ai3

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.12.5 Function of multifunctional inputs AI1, AI2 and AI3 The function of the multifunctional inputs AI1, AI2 and AI3 can be configured using parameter settings.
  • Page 56 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Function AI2 – Parameter P16 Parameter PI6 is used to set the function of the multifunctional input AI2. The multifunctional input AI2 can only be set using parameter P16 if DIP switch no.
  • Page 57: Functional Testing Of Connected Assemblies

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.13 Functional testing of connected assemblies The KaController provides the option of checking the function of the external units connected independently of the software application. The function of individual assemblies, such as the EC fan, can be directly activated and checked by means of inputs on the KaController.
  • Page 58: Parameter List For Control Pcb

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.14 Parameter list for control PCB Position Standard Unit Remark P000 Software version P001 °C Basic setpoint for setpoint input ± 3K...
  • Page 59 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) Position Standard Unit Remark P044 Function of digital input DI2 P045 kOhm Threshold voltage for potentiometer that switches on the unit...
  • Page 60 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Position Standard Unit Remark P086 Dependence of idronic algorithms Slave 6 P087 Dependence of idronic algorithms Slave 7 P088 Dependence of idronic algorithms Slave 8...
  • Page 61: Kacontroller Parameters

    Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1) 10.15 KaController parameters 10.15.1 General Specific user requirements can be enabled and disabled by means of parameter settings in the KaController, for instance the minimum and maximum setpoint temperature can be set using parameters in the KaController.
  • Page 62: Kacontroller Parameter List

    Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains 10.15.3 Parameterliste KaController Position Standard Unit Remark t001 Serial address t002 Baud rate 0 = Baud rate 4800 1 = Baud rate 9600...
  • Page 63 Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains Electrical wiring | UniLine EC, KaControl model (*C1)
  • Page 64 Electrical wiring | UniLine EC, KaControl model (*C1) Kampmann Assembly and Installation Instructions - UniLine Cassette Door Air Curtains...
  • Page 66 Kampmann GmbH & Co. KG Kampmann UK Ltd. Friedrich-Ebert-Str. 128 - 130 Dial House, Govett Avenue 49811 Lingen (Ems) Shepperton, Middlesex, TW17 8AG Germany Great Britain +49 591 7108-660 +44 (0)1932 228592 +49 591 7108-173 +44 (0)1932 228949 export@kampmann.de info@kampmann.co.uk...

This manual is also suitable for:

Uniline 15Uniline 20Uniline 25

Table of Contents