4.2 Rack Mounting

There are two mounting brackets installed on the front left and right side of the power system
to enable you to securely fasten the sub-rack to a cabinet or an open frame.
NOTE For ease of mounting the power rack it is recommended to remove the rectifiers.
NOTE When mounting the system to an open frame, the brackets should be moved to
the middle position.
To mount the subrack into a cabinet, follow the steps below:
1. Determine the installation position according to system measurement. Refer to the
Appendix A for details. Re-install the mounting bracket in another position if necessary.
Refer to the figure 4-1 below.

Figure 4-1 System Mounting - Cabinet

2. Place the system into the cabinet.
3. Fasten the system into the cabinet by using four M6 x 12mm screws and mounting
brackets on the front left and right side of the unit. Tighten the screws to 6 Nm.
24
Two ways to install mounting
brackets in the front position
+1 (208) 635-6400 | www.transtector.com
To mount the system into an open frame, follow the steps below:
1. Determine the installation position according to system measurement. Refer to the
Appendix A for details.
2. Remove the mounting brackets on the front left and right side of the system.
3. Refix the mounting brackets to the middle left and right side of the system.
4. Place the system into the open frame.
5. Fasten the system to the open frame by using four M6 x 12mm screws and the mounting
brackets. Tighten the screws to 6 Nm.

Figure 4-2 System Mounting - Open frame / relay rack

+1 (208) 635-6400 | www.transtector.com
Two ways to install mounting
brackets in the front position
25