Chapter 6 Maintenance & Troubleshooting; Maintenance; Checking Terminal Connection; Other Requirements - Infinite Transtector DCIPS2B-S-00-B11 Installation Manual

Power supply system
Table of Contents

Advertisement

Installation Manual
| DCIPS2B-S-00-B11 Power Supply System
Chapter 6 Maintenance & Troubleshooting

6.1 Maintenance

6.1.1 Checking Terminal Connection

The connections on the terminal blocks and circuit breakers must be checked according to
the Table 6-1 at least once a year.
TYPE OF CONNECTION
Terminal block for rail
Terminal block for rail
Front terminal for copper cables
Terminal block Weidemullers
Terminal block Weidemullers
Terminal block Weidemullers
Miniature circuit breaker
Miniature circuit breaker
Miniature circuit breaker
Miniature circuit breaker
Molded case circuit breaker
Molded case circuit breaker
Molded case circuit breaker
Molded case circuit breaker
Connection unit for 2 or 3 pole breaker Merlin G & Siemens
Terminal Block Phoenix
Terminal block Phoenix
Terminal block Phoenix
Terminal block Phoenix
Miniature circuit breaker

Table 6-1 Connection Torque Setting Check

6.1.2 Other Requirements

At least once a year the output voltage should be verified to be within acceptable limits. The
result of the test should be recorded and filed to see any deviations.
In addition, the system requires periodic inspections and routine cleaning. It is very important
to keep the all areas and components of the system free from dust or other unwanted
objects to ensure free air circulation and safe operation of the system.
46
MODEL / DESCRIPTION
TORQUE
TORQUE
(Nm)
(Inch LB)
AKG 16mm²
2.5
22
AKG 35mm²
3.5
31
FC Cu T2 95mm²
7.0
62
WDU 4mm
0.6
WDU 10mm
2.0
18
WDU 16mm
3.0
27
Siemens
2.5
22
Merlin G
3.5
31
ABB
2.0
18
CBI HY-MAG
3.0
27
ABB 160A - S2
5.0
45
ABB 160A/250A - S3/S4
9.0
80
ABB 630A - S6
9.0
80
Terasaki - XS125CJ
9.0
80
13.5
120
Phoenix Mini Combicon
0.25
UK10 / UKLKG10
1.5-1.8
13-16
UK16 / USLKG16
1.5-1.8
13-16
UK35/UIK35/USKG35/UISKG35 3.2-3.7
28-33
Nadar
2.5
22
+1 (208) 635-6400 | www.transtector.com

6.2 Troubleshooting

This troubleshooting chapter helps to determine the cause of the problem and suggests
possible repair solutions. If the first step of the recommendation does not solve the problem
continue to the next one.
NOTE If the malfunctioning of the system persists, please contact TRANSTECTOR
technical support.
NOTE For a description of Alarms and Messages generated by the system controller see
the Alarms/Messages section of the controller manual:
By default, alarms are set to be indicated with a red light (higher priority) and messages
5
with a yellow light (lower priority).
Fault
Low System
Voltage
High System
Voltage
Mains Error
2
AC Low Voltage
AC High Voltage AC voltage rises above the set limit.
+1 (208) 635-6400 | www.transtector.com
www.transtector.com
Possible Cause
Suggestion/Solution
Module failure.
Replace faulty module.
Loss of AC power.
Verify AC input connection.
Load exceeds module capacity.
Add module to system.
Module failure.
Replace the faulty module.
System voltage exceeds the set limit.
Check the High Voltage Alarm limit
setting.
AC supply OFF on one rectifier in the
Verify that the AC input breaker is
system with one plugged in rectifier.
ON.
AC supply OFF on at least two
Verify AC input connection.
rectifiers in the system with minimum
two plugged in rectifiers.
AC voltage drops below the set limit.
Verify the Low AC voltage limit
setting.
Verify AC Input connection.
Verify AC Input voltage.
Verify the High AC voltage limit.
Verify the AC Input voltage.
47

Advertisement

Table of Contents
loading

Table of Contents