4.1.3 Tools

The following tools are required for a safe installation of the system:
Anti-static hand strap.
Socket wrench, insulated.
Screwdriver set, flat, insulated.
Screwdriver set, torx, insulated.
Screwdrivers, pozidrive (cross head), sizes 1, 2, and 3, insulated.
Torque spanner (for battery connection), insulated.
WARNING Use only single-ended, fully insulated tools. Shafts of screwdrivers etc. should
be insulated.
CAUTION
Installation in USA / Canada must conform with the requirements in
NEC/CEC.
CAUTION Care must be taken when installing this system. The units can be damaged
and can cause damage if not handled with care. Pay particular attention to the order in
which units are installed.
22
+1 (208) 635-6400 | www.transtector.com
+1 (208) 635-6400 | www.transtector.com

4.1.4 Cable Size

Please use the recommended cable size given below for the system installation.
Port
Current
Cable Size
Max.
Min.(mm²)
AC Input -L1
32A
10mm²
AC Input -L2
32A
10mm²
AC Input -L3
16A
10mm²
AC Input -N
32A
10mm²
AC Input -PE
-
10mm²
Battery MCB
80A
20mm²
Battery MCB
100A
25mm²
Battery MCB
125A
35mm²
DC Load -MCB
63A
16mm²
DC Load -MCB
50A
14mm²
DC Load -MCB
40A
10mm²
DC Load -MCB
32A
8mm²
DC Load -MCB
25A
8mm²
DC Load -MCB
20A
6mm²
DC Load -MCB
16A
4mm²
DC Load -MCB
10A
2.5mm²
DC Load -MCB
6A
2.5mm²
DC Load -MCB
4A
1.5mm²

Table 4-1 Recommended Electrical Cable Size

Circuit Breakers must not exceed the below loading based on maximum 55°C operating
ambient:
For load breaker rated 5 to 32A, the maximum load must not exceed 80% of rating value.
For load breaker rated up to 63A, the maximum load shall not exceed 40A if space is
provided between breakers. Maximum 30A is allowed if no space provided.
For battery breaker rated up to 80A, the maximum load shall not exceed 80% of rating
value.
For battery breaker rated 100 to 125A, the maximum load shall not exceed 75A.
Cable Size
Temperature
Min.(AWG)
Rating
7 AWG
105°C
7 AWG
105°C
7 AWG
105°C
7 AWG
105°C
7 AWG
105°C
4 AWG
105°C
3 AWG
105°C
2 AWG
105°C
5 AWG
105°C
6 AWG
105°C
7AWG
105°C
8 AWG
105°C
8 AWG
105°C
9 AWG
105°C
10 AWG
105°C
14 AWG
105°C
14 AWG
105°C
15 AWG
105°C