6.8.2 Field wiring: Overview

RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
NOTICE
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
NOTICE
NEVER remove a thermistor, sensor, etc., when connecting power wiring and
transmission wiring. (If operated without thermistor, sensor, etc., the compressor
may break down.)
NOTICE
The reversed phase protection detector of this product only functions when the
product starts up. Consequently reversed phase detection is not performed
during normal operation of the product.
The reversed phase protection detector is designed to stop the product in the
event of an abnormality when the product is started up.
Replace 2 of the 3 phases (L1, L2, and L3) during reverse-phase protection
abnormality.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes on and off while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.
Field wiring consists of power supply (always including earth) and indoor-outdoor
communication (= transmission) wiring.
Example:
a
d
i
c
b
a
b
c
e
h
h
f
a Field power supply (with earth leakage protector)
b Main switch
c Earth connection
d Outdoor unit
e Indoor unit
f User interface
g Indoor power supply wiring (sheathed cable) (230 V)
h Transmission wiring (sheathed cable) (16 V)
i Outdoor power supply wiring (sheathed cable)
Power supply 3N~ 50 Hz
Power supply 1~ 50 Hz
Earth wiring
d
d
h
h
g
g
e
e
h
h
h
h
f
f
6
Installation
|
Installer and user reference guide
77