6.7.9 Checks after charging refrigerant

6.7.10 To fix the fluorinated greenhouse gases label

RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
Code
Indicates an indoor unit which
is not compatible with leak
detection functionality is
installed (e.g., RA DX indoor
unit, Hydrobox, ...)
Other
malfunction
code
Are all stop valves open?
Is the amount of refrigerant, that has been added, recorded on the refrigerant
charge label?
NOTICE
Make sure to open all stop valves after (pre-) charging the refrigerant.
Operating with the stop valves closed will damage the compressor.
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
f
GWP: XXX
2
1
+
1
GWP × kg
1000
a If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Quantity of fluorinated greenhouse gases of the total refrigerant charge
expressed as tonnes CO
f GWP = Global warming potential
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
Formula to calculate the quantity in CO
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label. That GWP is based on
the current legislation on fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.
2 Fix the label on the inside of the outdoor unit near the gas and liquid stop
valves.
Cause
a
kg
b
1
=
kg
c
2
=
kg
d
2
=
=
e
tCO
eq
2
equivalent.
2
2
6
Installation
|
Solution
Refer to requirements to be
able to execute leak detection
operation.
Close valve A immediately.
Confirm the malfunction code
and take corresponding action,
"10.2 Solving problems based
4
on error
codes" [
 116].
equivalent.
2
equivalent tonnes: GWP value of the
Installer and user reference guide