5
|
Preparation
Installer and user reference guide
42
Pattern 1
a
b
a
b
a
b
a To indoor unit
b Piping between outdoor units
X Not allowed (oil remains in piping)
O Allowed
▪
To avoid the risk of oil retention to the outmost outdoor unit, always connect the
stop valve and the piping between outdoor units as shown in the 4 correct
possibilities of the figure below.
a
b
b
a
b
b
a
a
b
a
a
a To indoor unit
b Oil collects to the outmost outdoor unit when the system stops
X Not allowed
O Allowed
▪
If the piping length between the outdoor units exceeds 2 m, create a rise of
200 mm or more in the gas line within a length of 2 m from the kit.
If
≤2 m
b
b
a
b
b
a
b
a
≤2 m
Pattern 2
a
b
a
b
a a
b
Then
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10