Charging Refrigerant; Precautions When Charging Refrigerant - Daikin VRV IV+ Installer And User Reference Manual

Table of Contents

Advertisement

6.7 Charging refrigerant

6.7.1 Precautions when charging refrigerant

RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
WARNING
Only use R410A as refrigerant. Other substances may cause explosions and
accidents.
R410A contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 2087.5. Do NOT vent these gases into the atmosphere.
When charging refrigerant, always use protective gloves and safety glasses.
NOTICE
If the power of some units is turned off, the charging procedure cannot be finished
properly.
NOTICE
In case of a multiple outdoor system, turn on the power of all outdoor units.
NOTICE
Be sure to turn on the power 6 hours before operation in order to have power
running to the crankcase heater and to protect the compressor.
NOTICE
If operation is performed within 12 minutes after the indoor and outdoor units are
turned on, the compressor will not operate before the communication is established
in a correct way between outdoor unit(s) and indoor units.
NOTICE
Before starting charging procedures, check if the 7‑segment display indication of the
outdoor unit A1P PCB is as normal (see
malfunction code is present, see
codes" [
4
 116].
NOTICE
Make sure all connected indoor units are recognised (see [1‑10], [1‑38] and [1‑39] in
"7.2.7 Mode 1: Monitoring
settings" [
NOTICE
Close the front panel before any refrigerant charge operation is executed. Without
the front panel attached the unit cannot judge correctly whether it is operating
properly or not.
NOTICE
In case of maintenance and the system (outdoor unit+field piping+indoor units) does
not contain any refrigerant any more (e.g., after refrigerant reclaim operation), the
unit has to be charged with its original amount of refrigerant (refer to the nameplate
on the unit) by pre-charging before the automatic charging function can be started.
"7.2.4  To access mode 1 or 2" 
"10.2  Solving problems based on error
4
 89]).
Installer and user reference guide
6
Installation
|
4
[
  86]). If a
63