Preparation; Overview: Preparation; Preparing The Installation Site; Installation Site Requirements Of The Outdoor Unit - Daikin VRV IV+ Installer And User Reference Manual

Table of Contents

Advertisement

5 Preparation

5.1 Overview: Preparation

5.2 Preparing the installation site

5.2.1 Installation site requirements of the outdoor unit

RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
This chapter describes what you have to do and know before going on-site.
It contains information about:
Preparing the installation site
Preparing the refrigerant piping
Preparing the electrical wiring
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Select a place where rain can be avoided as much as possible.
Select the location of the unit in such a way that the sound generated by the unit
does not disturb anyone, and the location is selected according the applicable
legislation.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
NOTICE
This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires keeping
proper distances away from stereo equipment, personal computers, etc.
5
Preparation
|
Installer and user reference guide
25

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents