9.3. System overview of field wiring
(See figure 9)
1
Earth leakage breaker
2
Field fuse
3
Remote controller
9.4. Precautions on wiring of power supply and
inter-unit wiring
Let the power wire (including ground wire and if applicable, the
bottom plate heater wire) go through the power outlet port on
either the front, side or back of the outdoor unit.
Let the transmission wires go through the cable outlet port, pipe
outlet port or knock out hole on either the front, side or back of
the outdoor unit.
(See figure
A
Rear direction
B
Lateral direction
C
Front direction
1
Power terminal block (X1M)
2
Control wiring between units
3
Power cable with ground wire. (Keep proper distance between
power cable and control wiring).
4
Clamp (field supply)
5
Stop valve mounting plate
6
Power cable
7
Ground cable (yellow/green)
8
Fix the control wiring with the clamp
9
Control terminal block (X2M)
10
Interconnection cable for bottom plate heater (ERRQ only)
Precautions when knocking out knockout holes
To punch a knock hole, hit on it with a hammer.
After knocking out the holes, we recommend you paint the
edges and areas around the edges using the repair paint to
prevent rusting.
When passing electrical wiring through the knock holes, remove
any burrs from the knock holes and wrap the wiring with
protective tape to prevent damage.
If there is any possibility that small animals enter the system
through the knock holes, plug the holes with packing materials
(to be prepared on-site).
1
2
1
Knockout hole
2
Burr
3
Packing materials
Installation manual
15
8).
3
Use a power wire pipe for the power wiring.
Outside the unit, make sure the low voltage electric
wiring (i.e. for the remote control, between units, etc.)
and the high voltage electric wiring do not pass near
each other, keeping them at least 50 mm apart.
Proximity
may
malfunctions, and breakage.
Be sure to connect the power wiring to the power
wiring terminal block and secure it as described under
"9.4. Precautions on wiring of power supply and
inter-unit wiring" on page
Inter-unit wiring should be secured as described in
"9.4. Precautions on wiring of power supply and
inter-unit wiring" on page
Secure the wiring with clamps so that it does not
touch the piping.
Make sure the wiring and the electric box lid do not
stick up above the structure, and close the cover
firmly.
9.5. Specifications of standard wiring components
A power circuit (see table below) must be provided for connection of
the unit. This circuit must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage breaker.
ERSQ_V1 ERRQ_V1 ERSQ_Y1 ERRQ_Y1
Phase and frequency
Voltage
Recommended field fuse
(a)
Minimum circuit amps
Transmission line section
(b)
Wire type
(a) Stated values are maximum values (see electrical data of combination with
indoor units for exact values).
(b) Only in protected pipes, use H07RN-F when protected pipes are not used.
NOTE
Select the power supply cable in accordance with
relevant local and national regulations.
Wire size must comply with the applicable local
and national code.
Specifications for local wiring power cord and
branch wiring are in compliance with IEC60245.
The earth leakage circuit breaker must be a
high-speed type breaker of 300 mA (<0.1 s).
In connecting the power cable to the power terminal block,
securely clamp the cable as shown in
After finishing the electric work, confirm that each electric
part and terminal inside the electric parts box is connected
securely.
For V1 models only : Equipment complying with EN/IEC 61000-3-12
(1) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and ≤75 A per phase.
cause
electrical
interference,
15.
15.
1N~ 50 Hz
3N~ 50 Hz
220-240 V
380-415 V
32 A
16 A
27 A
27.5 A
13.5 A
2
0.75~1.25 mm
H05VV
figure
8.
ERSQ+ERRQ011~016AAV1+Y1
Outdoor unit for air to water heat pump
4PW49635-1C
14 A
(1)
.