Preparation

5.4.2 About electrical compliance

Installer and user reference guide
44
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by
the safety devices required by the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
This equipment complies with:
EN/IEC 61000‑3‑11 provided that the system impedance Z
to Z
at the interface point between the user's supply and the public system.
max
-
EN/IEC 61000‑3‑11 = European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated current ≤75 A.
-
It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected only to a supply with a system impedance Z
or equal to Z
.
max
EN/IEC 61000‑3‑12 provided that the short-circuit power S
equal to the minimum S
and the public system.
-
EN/IEC 61000‑3‑12 = European/International Technical Standard setting the
limits for harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.
-
It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected only to a supply with a short-circuit power S
than or equal to the minimum S
Model
RYYQ8/RYMQ8/RXYQ8
RYYQ10/RYMQ10/RXYQ10
RYYQ12/RYMQ12/RXYQ12
RYYQ14/RYMQ14/RXYQ14
RYYQ16/RYMQ16/RXYQ16
RYYQ18/RYMQ18/RXYQ18
RYYQ20/RYMQ20/RXYQ20
RYYQ22/RXYQ22
value at the interface point between the user's supply
sc
value.
sc
Z
max
is less than or equal
sys
sys
is greater than or
sc
(Ω)
Minimum S
(kVA)
4050
5535
6038
6793
7547
8805
9812
11573
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
less than
greater
sc
value
sc