Charging refrigerant
19.9 To check refrigerant piping joints for leaks after charging refrigerant
Installer and user reference guide
124
Tightness test of field-made refrigerant joints indoors
1 Use a leakage test method with a minimum sensitivity of 5 g of refrigerant/
year. Test leaks using a pressure of at least 0.25 times the maximum working
pressure (see "PS High" on the unit nameplate).
If a leak is detected
1 Recover the refrigerant, repair the joint, and repeat the test.
2 Perform the leak tests see
3 Charge refrigerant.
4 Check for refrigerant leaks after charging (see above).