Commissioning, inspection, maintenance
Adjusting pump rate of integral circulation pump
Curve
Pump rate of circulation pump
A
B
C
D
E
F
G
H
K
L

Activating screed drying

Screed drying
Six different temperature profiles can be set for screed
drying:
Default temperature profiles can be set in "System
configuration".
For further details, see "Function description".

Leak test on balanced flue system (annular gap check)

A
Fig. 29
Combustion air aperture
A
For balanced flue systems tested together with the
heat generator, there is no requirement for a tightness
test (overpressure test) during commissioning by the
flue gas inspector.
In this case, we recommend that a simple tightness
test is carried out during system commissioning. For
this, check the CO
or O
2
2
tion air at the annular gap of the balanced flue pipe.
44
10 %
20 %
30 %
40 %
50 %
60 %
70 %
80 %
90 %
100 %
concentration in the combus-
(cont.)
Note
Screed drying applies to all connected heating circuits
simultaneously. DHW heating is not possible during
screed drying.
If the CO
concentration is less than 0.2 % or the O
2
concentration is greater than 20.6 %, the flue pipe is
deemed to be sufficiently gas-tight.
If actual CO
values are greater or O
2
then pressure test the flue pipe with a static pressure
of 200 Pa.
2
values are lower,
2