On-Site Connections On The Hmbu Heat Management Unit; Outside Temperature Sensor; Connecting The Low Loss Header Sensor ) - Viessmann Vitodens 100-W B1HF Series Installation And Service Instructions Manual

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Installation sequence
Electrical connections
Cylinder temperature sensor (system boiler)
E
X
Equipotential bonding (earth conductor)

On-site connections on the HMBU heat management unit

A
Fig. 15
Diaphragm grommets, 230 V cables
A
Diaphragm grommets, extra low voltage (ELV)
B

Outside temperature sensor

Fitting location for outside temperature sensor
North or north-westerly wall, 2 to 2.5 m above
ground level; in multi storey buildings, in the upper
half of the second floor
Not above windows, doors or vents
Not immediately below balconies or gutters
Never render over.
Connecting the low loss header sensor
The sensor of the low loss header is connected to the
accessory extension EM-P1 or EM-M1/MX (ADIO elec-
tronics module) respectively.
24
(cont.)
B
)
Note on connecting accessories
When connecting accessories observe the sep-
arate installation instructions provided with
them.
Open diaphragm grommets as required. Thread
through only one cable at a time without a plug.
Ensure diaphragm grommets are airtight. If required,
remove plug from cable. After threading the cable
through, re-fit the plug to the wire ferrules.
For cables without strain relief bushings, provide
strain relief in the wiring chamber in the form of cable
ties.
Outside temperature sensor connection
See page 23
2-core lead, length up to 35 m with a cross-section
of 1.5 mm
2
See installation instructions for extension EM-P1
or EM-M1/MX