Accessories Mains Connection, Connect Plug To External Power Supply; Power Supply Fö - Viessmann Vitodens 100-W B1HF Series Installation And Service Instructions Manual

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Installation sequence
Electrical connections

Accessories mains connection, connect plug to external power supply

Connect one or more extensions via an ON/OFF
switch directly to the mains supply (see next chapter).
Accessories with direct mains connection
A
PlusBus
E
Fig. 17
HBMU heat management unit, heat generator
A
Mixer extension kit (ADIO electronics module)
B
EM-EA1 extension (DIO electronics module)
C
and/or EM-S1 extension (ADIO or SDIO/SM1A
electronics module)
Note
PlusBus system length max. 50 m for 0.34 mm
cross-section and unshielded cable.
If the current flowing to the connected working parts
(e.g. circulation pumps) is higher than the fuse rating
of the relevant accessory, only use the output con-
cerned to control an on-site relay.
Note
Use addressing for rotary selector S1. See also the
note in chapter "Information on connecting PlusBus
subscribers".
Accessories
EM-M1, EM-MX mixer exten-
sion kit
EM-EA1 extension
EM-S1 extension (not for Vito-
dens 111-F)
Power supply
Danger
Incorrectly executed electrical installations can
result in injuries from electrical current and dam-
age to the appliance.
Connect the power supply and implement all
safety measures (e.g. RCD circuit) in accord-
ance with the following regulations:
IEC 60364-4-41
VDE regulations
Connection conditions of the local grid opera-
tor
26
(cont.)
B
C
2
cable
Internal fuse protec-
tion
2 A
2 A
2 A
D
EM-P1 extension (ADIO electronics module)
D
E
ON/OFF switch
Mains input
A Power outlet
PlusBus
jF
Danger
Incorrect wiring can lead to serious injury from
electrical current and result in appliance dam-
age.
Route extra low voltage (ELV) leads < 42 V
separately from cables
Strip as little of the insulation as possible,
directly before the terminals, and bundle close
to the corresponding terminals.
Secure cables/leads with cable ties.
Install an isolator in the power cable to provide
omnipolar separation from the mains for all active
conductors, corresponding to overvoltage cate-
gory III (3 mm) for complete isolation. The isolator
must be fitted in the permanent electrical installation,
in line with installation requirements.
We also recommend installing a pulse current-sensi-
tive RCD (RCD class A
Connect the power cable to the electricity supply
using a fixed connection.
42 V/230 V~.
>
).