Viessmann Vitodens 100-W B1HF Series Installation And Service Instructions Manual page 43

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Adjusting pump rate of integral circulation pump
100
Min
+30
+20
Outside temperature in °C
Fig. 27
Setting (%) in system configuration. See page 56.
Residual head of integral circulation pump
600
60
L
550 55
K
500 50
450 45
H
400
40
350 35
G
300
30
250 25
F
200
20
E
150 15
D
100
10
50
C
5
B
A
0
0
0
100
200
Flow rate in l/h
Fig. 28
Upper operational limit
M
Max
-20
-30
300
400
500
600
700
Commissioning, inspection, maintenance
In the delivered condition, the minimum pump rate
and the maximum pump rate are set to the following
values:
Rated heating output
in kW
11
19
25
32
In the following system conditions, the internal circu-
lation pump is operated at a constant speed:
Low loss header or heating water buffer cylinder
and heating circuits with mixer
Constant operation
800
900
1000
1100
1200
(cont.)
Speed settings in the de-
livered condition in %
Min. pump
Max. pump
rate
rate
40
40
40
40
M
1300 1400
60
65
75
100
43