Checking The Combustion Quality - Viessmann Vitodens 100-W B1HF Series Installation And Service Instructions Manual

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Checking the combustion quality

The electronic combustion controller automatically
ensures optimum combustion quality. During commis-
sioning/maintenance, only the combustion values need
to be checked. To do this, test the CO content and CO
or O
content, and record these in the report on
2
page 97.
Permissible CO content
The CO content must be < 1000 ppm for all gas types.
Permissible CO
or O
2
Operation with natural gas
Rated heating out-
CO
put (kW)
Upper heating out-
put
11
7.3 - 10.5
19
7.5 - 10.5
25
7.5 - 10.5
32
7.3 - 10.0
Operation with LPG
CO
content: 8.4 - 11.8 %
2
O
content: 3.1 - 8.1 %
2
If the actual CO, CO
or O
2
respective ranges, proceed as follows:
Check the balanced flue system for leaks; see
page 44.
Check the ionisation electrode and connecting cable,
see page 48.
Note
During commissioning, the combustion controller car-
ries out an automatic calibration. Allow approx. 50 s
after the burner has started before testing the emis-
sions.
1. Connect a flue gas analyser at flue gas port
the boiler flue connection.
2. Open the gas shut-off valve. Start the boiler. Cre-
ate a heat demand.
3. Adjust the lower heating output. See the following
chapter.
4. Check the CO
content. If the actual value deviates
2
from the permissible ranges, implement steps lis-
ted above.
5. Enter the actual value into the report.
54
content
2
content (%)
2
Lower heating out-
put
7.3 - 10.5
7.5 - 10.5
7.5 - 10.5
7.3 - 10.5
values lie outside their
2
A
Note
To prevent operating faults and damage, operate the
appliance with uncontaminated combustion air.
2
O
content (%)
2
Upper heating out-
put
2.1 - 7.9
2.1 - 7.6
2.1 - 7.6
3.1 - 7.9
Fig. 39
on
6. Adjust the upper heating output. See the following
chapter.
7. Check the CO
2
from the permissible ranges by more than 1 %,
implement steps listed above.
8. Enter the actual value into the report.
9. Re-seal test port
Danger
Escaping flue gas can damage your health.
Check test port
Lower heating out-
put
2.1 - 7.9
2.1 - 7.6
2.1 - 7.6
2.1 - 7.9
A
content. If the actual value deviates
.
A
A
for leaks.