DHW heating

The burner, the circulation pump and the 3-way
diverter valve are started or changed over if the cylin-
der temperature lies 2.5 K below the set cylinder tem-
perature.
In the delivered condition, the set boiler water temper-
ature is 20 K higher than the set cylinder temperature.
If the actual cylinder temperature exceeds the set cyl-
inder temperature by 2.5 K, the burner shuts down and
circulation pump run-on begins.

External heating circuit hook-up (if installed)

Note
Only in conjunction with weather-compensated opera-
tion.
Danger
Risk of injury due to increased DHW tempera-
ture.
Inform the system user of the risk from the
raised outlet temperature at the draw-off points.
Gas condensing system boiler:
If the set DHW temperature is set to over
60 °C
Gas condensing combi boiler:
If there are several draw-off events in quick
succession or several appliance calibration
processes
Function:
If the external demand is active (plug 96 or digital
input on EM-EA1 (DIO) electronics module closed),
the heating circuit is supplied with heat.
If the external demand is inactive (contact open),
heat supply to the heating circuit ends (regardless
of the current set room temperature or the switch-
ing time).
!
Please note
There is no frost protection for the connec-
ted heating circuits.
Connection:
If only one heating circuit is hooked up, use con-
nection at plug 96: See page 25.
If multiple heating circuits are hooked up, connect
all contacts to EM-EA1 extension (DIO electronics
module) with the subscriber number. 1 (rotary
switch = 1).
See EM-EA1 extension installation instruc-
tions
Note
Perform the hook-up with subscriber number "1".
Function description
93