Viessmann Vitodens 100-W B1HF Series Installation And Service Instructions Manual page 35

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Commissioning the system
Commissioning assistant
sequence
"C.10"
EM-EA1 (DIO) function
"C.11"
Date (day, month, year)
"C.12"
Time (hours, minutes)
"C.13"
Autom. summer/wintertime
changeover
"C.14"
Plug 96 function
"C.15"
Remote control
Maintenance
Interval in burner hours run
until next maintenance
Interval until next mainte-
nance
The system carries out a restart.
Automatic flue gas temperature sensor check
The display shows: "Err"
If the flue gas temperature sensor is not positioned
correctly, fault message 416 appears.
For further details regarding the flue gas temperature
sensor test, see "Repairs".
If fault message 416 appears, reposition the flue gas
temperature sensor in the flue gas connection. Check
for leaks on the flue gas side.
(cont.)
Explanations and references
0 - No function
4 - External set flow temperature 0-10 V
5 - External default output
8 - 230 V fault message input and fault message output (without system
blocking)
10 - External extractor (e.g. cooker hood)
11 - Operating mode changeover
14 - Fault message input (24 V) and system blocking (e.g. condensate lift
pump)
16 - External LPG valve
17 - 230 V fault message input and system blocking
18 - External demand (digital)
19 - External blocking
ON = on
OFF = off
0 - No function
2 - External demand DHW circulation pump
4 - External demand
5 - External blocking
If only one HC was configured with external hook-up, plug 96 setting is auto-
matically applied. No selection or other function is then possible.
Off - not installed
ON - Vitotrol 200-E with subscriber number 1 installed (all installed heating
circuits can be controlled via the Vitotrol 200-E)
After the final setting (C.15) has been completed, "End" appears on the dis-
play. Confirm with "OK".
The commissioning is started, the flue temperature sensor test is launched
and "Fst" appears on the display.
Can be adjusted via the software tool (notification also via software tool)
Can be adjusted via the software tool (notification also via software tool)
Note
The burner remains locked out until the test has been
passed.
When the fault has been remedied, turn the ON/OFF
switch off and back on again.
Commissioning, inspection, maintenance
35