Terminals - VAN DER ENDE Vacon 100 Flow Manual

Table of Contents

Advertisement

6.2.2.2 Terminals

According to the settings of PID control 6.2.2.1
Basic I/O board
terminal
1
+10 V
Reference output
ref
Analogue input, 0 to 10 V DC or
2
AI 1+
0/4 to 20 mA
Analogue input reference
3
AI 1-
potential
Analogue input, 0 to 10 V DC or
4
AI 2+
0/4 to 20 mA
Analogue input reference
5
AI 2-
potential
6
+ 24 V
Output voltage control
7
GND
I/O reference potential
8
DI 1
Digital input 1
9
DI 2
Digital input 2
10
DI 3
Digital input 3
Additional reference potential
11
CM
for DI 1 to DI 6
12
+ 24 V
Output voltage control
13
GND
I/O reference potential
14
DI 4
Digital input 4
15
DI 5
Digital input 5
16
DI 6
Digital input 6
Additional reference potential
17
CM
for DI 1 to DI 6
18
AO 1+
Analogue output
19
AO-/GND
30
+24 V in 24 V input voltage
A
RS-485
B
RS-485
21 RO1 nc
22 RO1 com
23 RO1 no
24 RO2 nc
25 RO2 com
26 RO2 no
32 RO3 com
33 RO3 no
signal
Power supply for potentiometer, etc.
Voltage input frequency reference
Reference potential inputs and outputs
Programmable current input
Power supply for contacts, etc. max 0.1 A
Reference potential inputs and outputs
Start PID (programmable contact)
External error if contact is broken
(programmable contact)
reset failure (programmable contact)
Is connected to GND (earth). Can also be
insulated from GND by jumpers
Power supply for contacts, etc. max 0.1 A
Reference potential inputs and outputs
Fixed frequency selection 0. (Binary)
(programmable contact)
PID reference 2 (programmable contact)
Switching between control signal source
(programmable contact)
Is connected to GND (earth). Can also be
insulated from GND by jumpers
Programmable
range 0 to 20 mA / R max 500.
Relay board 1
Relay output 1 Programmable (run)
Relay output 2 Programmable (fault)
Relay output 3 Programmable (ready)
description (PID settings)
Vacon 100 Flow
32