6.2.1.1 Application example: 0 - 10 V tracking control (using Default Wizard 6.2.1)

Parameter group
Motor settings
Motor control
P3.1.2.3
P3.1.2.4
Motor limits
P3.1.3.1
Start/Stop Settings
P3.2.4
P3.2.5
References
Frequency reference
P3.3.1.5
I/O Configuration
Analogue input 1
P3.5.2.1.2
P3.5.2.1.3
Protections
Motor thermal protection
P3.9.2.1
The 0 to 10 V signal is connected to AI 1 on the 2 (+) and 3 (to) terminals.
The tracking control is started by connecting 8 (DI 1) to 6 (+24 V).
Make sure that dipswitch AI 1 is in the Volt signal position (up).
Description
Internal switching frequency
Identification
Current limit
Start function
Stop function
I/O reference A
AI 1 signal filter time
AI 1 signal range
Calculated motor thermal
protection
Location and selection of dipswitch AI 1
Setting
Modification if excessive motor noise
Ad stand still (start within 30 sec)
Maximum permissible motor current ± 1.4x In
Ramping (pump)/Running start (fan)
Freewheel (fan)/Ramping (pump)
AI 1
0 sec.
0 to 10 V/0 to 20 mA
no action