6.2.2 PID-Control Application (Wizard)

Please note! The factory setting must always be used as a starting point when using the
application examples in this book. (P6.5.1)
With the PID control application Wizard, the following parameters appear:
Step
Parameter
1
Motor type
2
Rated voltage
3
Rated motor frequency
4
Rated motor speed
5
Rated motor current
6
Cos phi of the motor
7
Minimum frequency
8
Maximum frequency
9
acceleration time
10
deceleration
11
Control location
12
Selection of process unit
13
Minimum process unit
14
Maximum process unit
15
Decimal process unit
16
Feedback 1 source selection
17
Signal range analogue inputs
18
Inversion error
19
Reference point source selection
20
Control panel reference point 1
21
Sleep function?
22
Sleep frequency
23
Sleep delay 1
24
Wake-up level
Number
Description
P3.1.2.2
Permanent magnet or induction motor
P3.1.1.1
Varies
P3.1.1.2
8 to 320 Hz.
P3.1.1.3
24 to 19,200 rpm
P3.1.1.4
Varies
P3.1.1.5
0.3 to 1
P3.3.1.1
0 Hz. ... P3.3.1.2
P3.3.1.2
P3.3.1.1 ... 320 Hz.
P3.4.1.2
0.1 to 300 s
P3.4.1.3
0.1 to 300 s
I/O - terminals
Fieldbus
Control Panel
P3.13.1.4
Various options
P3.13.1.5
Minimum value of sensor, e.g. (0 - 10 bar) = 0 bar
P3.13.1.6
Maximum value of sensor, e.g. 10 bar
P3.13.1.7
Decimal places (0 to 0.0000)
P3.13.3.3
Position sensor, e.g. (AI 2)
0 to 10 V/0 to 20 mA
2 to 10 V/4 to 20 mA
P3.13.1.8
Normal/inverted
P3.13.2.6
Reference location PID (Control panel reference point 1)
P3.13.2.1
Fill in operating point
Yes/no
If no is selected, Wizard complete
P3.13.5.1
0 to 320 Hz.
P3.13.5.2
0 to 3,000 s
P3.13.5.3
Regulator starting point
Vacon 100 Flow
29
page