Setting The Station Communication; Verifying The Station Communication - ABB RET650 Series Commissioning Manual

Relion 650 series transformer protection
Hide thumbs Also See for RET650 Series:
Table of Contents

Advertisement

Section 7
Testing functionality
7.13.1.2

Setting the station communication

To enable the IEC 61850 communication, the corresponding COM03 ports must be activated. Port
LAN1 A and LAN1 B are used for redundancy.
If COM03 is used; the following below apply. If COM05 is used; there is no redundancy and the port
is named LAN1 or (FRONT)
To enable IEC 61850 station communication:
The IEC 61850-8-1 station communication functionality must be configured in the local HMI.
Navigate to Main Menu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB
and set the
communication, to
To enable GOOSE communication, the
function blocks (GOOSEBINRCV and GOOSEINTLKRCV) must be set to
application configuration.
To enable GOOSE communication via the front port the parameter
Configuration/Communication/Station communication/IEC61850-8-1/PortSelGOOSE must
be set to
must be set to
To enable IEC 61850 station communication:
1.
Enable IEC 61850-8-1 (substation bus) communication for port A and B.
1.1.
1.2.
2.
Enable redundant IEC 61850-8-1 communication for port A and B.
2.1.
7.13.1.3

Verifying the station communication

Connect a PC to the substation network and ping the connected IED and the Substation Master PC
to verify that the communication is working up to the transport layer.
The best way to verify the communication up to the application layer is to use a protocol analyzer
connected to the substation or process bus and monitor the communication.
84
OperationMode parameter to NonRedundant(A) or, for redundant
PRP(A+B) .
Front . To enable GOOSE communication via rear port the parameter PortSelGOOSE
LAN1 .
Set values for ETHLAN1_AB.
Navigate to Main Menu/Configuration/TCP-IP configuation/ETHLAN1_AB.
OperationMode , IPAddress and IPMask . OperationMode must be set to
Set values for
NonRedundantA .
Check that the correct IP address is assigned to the port.
Enable IEC 61850-8-1 communication.
Navigate to Main menu/Settings/General settings/Communication/Station
communication/IEC 61850-8-1.
Operation to Enabled and PortSelGOOSE to the port used.
Set
Enable redundant communication.
Navigate to Main Menu/Configuration/TCP-IP configuation/ETHLAN1_AB.
Set values for
OperationMode , IPAddress and IPMask . OperationMode must be set to .
Make sure that the optical fibres are connected correctly.
© Copyright 2013 ABB. All rights reserved
Operation parameter for the corresponding GOOSE
1MRK 504 136-UUS B
GUID-B77A38F2-1895-4CB3-AB16-961E8A73DAD5 v1
Enabled in the
GOOSE in Main menu/
GUID-0B7E64BC-3346-4105-90C0-2EA5A5BB74DE v1
Transformer protection RET650
Commissioning manual