2. INTRODUCTION
2.1 Inspection
Examine the shipping carton for any sign of damage. Inspect the
unit and any accessories for damage. If there is any damage,
consult your distributor immediately.
2.2 Description
The EZ365 is a socket tester that additionally checks the earth loop
impedance of the wiring under test and indicates the range that the
measured earth loop impedance falls within. If the wiring is faulty or
the mains voltage is not within limits the earth loop impedance test
is not performed.
The EZ365 also indicates if the mains voltage is below 195V or
above 270 V or if the neutral to earth voltage is greater than 30V.
The 'T Safe' technology employed by the EZ365 allows the earth
loop impedance to be measured with a 30mA or higher RCD in
circuit without it tripping.
Additional features of the EZ365 are:
¡ Buzzer indication of socket wiring.
¡ Polarity reversal check by means of a touch pad.
¡ RCD trip test for 30mA RCD's.
3