Dräger Polytron 6100 EC WL Instructions For Use Manual page 37

Hide thumbs Also See for Polytron 6100 EC WL:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 30
®
● If the Bluetooth
pairing PIN "000000" is used, Bluetooth
automatic.
®
If an individual Bluetooth
pairing PIN has been assigned, a prompt
requests entering the PIN.
✓ After successful connection, the blue LED lights up continuously.
Gas detector and Windowsterminal device with PolySoft are connected.
If required, use PolySoft to assign an individual Bluetooth
NOTICE
► Safeguard the individual Bluetooth
4.2.5
Connecting the ISA100 Wireless
● Connect the Windows mobile device with the respective management
station of the ISA100 Wireless
The configuration is done with PolySoft.
5
Mechanical installation
WARNING
Risk of explosion!
In potentially explosive atmospheres, electrostatic discharge may cause sparks
on the antenna.
► Do not install the antenna in explosion-hazard areas subject to intense
electrostatic charging, for example, due to fast moving particles or
pneumatic transport of powders.
WARNING
Risk of explosion!
In areas where there is a risk of dust explosion, electrostatic discharge may
cause sparks on the housing and sensing head.
► Do not install the gas detector in dust explosion-hazard areas subject to
intense electrostatic charging, for example, due to fast moving particles or
pneumatic transport of powders.
Instructions for use
|
Dräger Polytron
®
pairing is
®
pairing PIN.
®
pairing PIN.
interface
network.
®
6100 EC WL, Dräger Polytron
5.1
Installing the gas detector - installation
without mounting accessories
The gas detector is installed vertically on a flat surface.
For installation with mounting accessories, see corresponding assembly
instructions.
Prerequisites:
A suitable installation location is selected (see "Safety information", section
"Mechanical installation", page 32).
CAUTION
Risk of explosion!
The gas detector is not tested in environments with increased oxygen content
(> 21 % O
).
2
► Do not use the gas detector in environments with increased oxygen content.
Install the gas detector:
● Install the gas detector using the drilling template (see "Drilling template"
appendix) and M6 (1/4") hexagon socket head cap screws.
5.2
Installing the antenna
1. Remove the cover cap from the antenna connector (Fig. A 4).
2. Screw the antenna into the connector and tighten it by hand.
5.3
Installing the remote antenna
1. Remove the protective cap for the antenna on the connection (Fig. A 4).
2. Screw antenna cable to connection and tighten hand-tight.
3. Select an installation location where a perfect signal transmission is
ensured. The antenna must point up vertically.
4. Attach the mounting bracket at the installation location of the remote
antenna.
5. Lay the antenna cable.
®
Repeater ISA
|
en
Mechanical installation
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Polytron repeater isa

Table of Contents