The EE10 transmitter is ready to use and does not require any configuration by the user. The factory setup of EE10 corresponds to
the type number ordered. For ordering guide please see data sheet at www.epluse.com/ee10.
If need, the user can change the factory setup by using the optional Configuration Adapter Cable HA011066 and the E+E Product
Configuration Software (EE-PCS).
Configuration Adapter Cable HA011066
The user can change the display settings and perform one or two point adjustment for RH and T.
The free E+E Product Configuration Software (EE-PCS) and can be downloaded from www.epluse.com/configurator.
tECHNiCAL DAtA
measured values
relative humidity
Working range
Accuracy
at 20 °C
1)
Analogue (0-10 V, 4-20 mA)
Digital (RS485)
Temperature dependence
temperature
Accuracy
at 20 °C
1)
Output
analogue
(RH: 0...100 % RH / T: see ordering guide)
Digital interface
Protocol
temperature passive
general
Voltage supply (U
)
V
0 - 10 V
4 - 20 mA
RS485
Current consumption
Analogue (0-10 V, 4-20 mA)
Digital (RS485)
Electrical connection
Housing (polycarbonate)
Protection class
Display
CE compatibility according
Temperature working range
Temperature storage range
1) The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in
accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
0...95 % RH
and U
=24 V DC
(68 °F)
V
±2 % RH (40...60 % RH)
±3 % RH (30...70 % RH)
Traceable to intern. standards, administrated by NIST, PTB, BEV...
typical 0.06 % RH /°C
and U
=24 V DC
output A3: ±0.25 °C
(68 °F)
V
output: J3: ±0.3 °C
0-10 V
4-20 mA (two wires)
(0.03 % RH / °F)
(±0.45 °F)
(±0.54 °F)
RS485 with max. 32 devices on one bus
Modbus RTU or BACnet MS/TP
please see ordering guide
15 - 40 V DC or 24 V AC ±20%
10 + 0.02 x R
< U
< 28 V DC
L
V
15 - 35 V DC or 24 V AC ±20%
for DC supply: typ. 4 mA / for AC supply: typ. 15 mA
for DC supply: typ. 9 mA / for AC supply: typ. 20 mA
screw terminals max. 1.5 mm
US Version: UL94V-0 approved / EU Version: UL94HB approved
IP30
for EE10-M1
for EE10-M6
EN61326-1
EN61326-2-3
-5...55 °C
(23...131 °F)
-25...60 °C
(-13...140 °F)
±3 % RH (10...90 % RH)
±5 % RH (10...90 % RH)
output A6: ±0.4 °C
-1 mA < I
< 1 mA
L
R
< (U
-10)/0.02 < 500 Ohm
L
V
(R
< 500 Ohm)
L
eff
eff
2
(AWG 16)
Humidity / Temperature alternating
Humidity
(±0.72 °F)

Advertisement

loading