QS4500TE0001
Step 6: To view setpoints, press the <Display Select>
pushbutton until the Set Points LED lights. Use the
Table 1 Setpoint Possibilities
Setpoint
Setpoint Units
TDES
Minutes:Seconds
TDNE
Minutes:Seconds
TDEN
Minutes:Seconds
TDEC
Minutes:Seconds
NOMF
Volts
NOMV
Volts
1UVD
Volts
2UVD
Volts
1UVP
Volts
2UVP
Volts
1OVD
Volts
2OVD
Volts
1OVP
Volts
2OVP
Volts
1UFD
Hertz
2UFD
Hertz
1UFP
Hertz
2UFP
Hertz
1OFD
Hertz
2OFD
Hertz
1OFP
Hertz
2OFP
Hertz
TDN
Minutes:Seconds
TDNLD
LDCY
Volts
PRFSRC
EXER
EXLD
PEDAY
PEH
PEMIN
MANTR
CTDNE
TMODE
TER
Hours:Minutes
TPRE
Minutes:Seconds
GENNO
PHASE
TSEQ
Minutes:Seconds
PT
TDEF
Seconds
Effective 6.01
<Step> pushbutton to step through the set points
(Figure 6 and Table 1).
Description
Time Delay Engine Start
Time Delay Normal to Emergency
Time Delay Emergency to Normal
Time Delay Engine Cooloff
Nominal Frequency
Nominal Voltage
Source 1 Undervoltage Dropout
Source 2 Undervoltage Dropout
Source 1 Undervoltage Pickup
Source 2 Undervoltage Pickup
Source 1 Overvoltage Dropout
Source 2 Overvoltage Dropout
Source 1 Overvoltage Pickup
Source 2 Overvoltage Pickup
Source 1 Underfrequency Dropout
Source 2 Underfrequency Dropout
Source 1 Underfrequency Pickup
Source 2 Underfrequency Pickup
Source 1 Overfrequency Dropout
Source 2 Overfrequency Dropout
Source 1 Overfrequency Pickup
Source 2 Overfrequency Pickup
Time Delay Neutral
Load Decay Neutral
Load Decay Voltage
Preferred Source
Clock Exerciser
Exercise Load Transfer
Exercise Day
Clock Exercise Hour
Clock Exercise Minute
Retransfer Mode
Commit/No Commit
Engine Test Mode (Pushbutton)
Engine Test/PE Run Time
Pre Transfer Signal Time
Number of Generators
Phases
Time Delay Load Sequencing
PT Ratio
Time Delay Engine Fail
Range
Factory Default
0 to 120 seconds
0
0 to 1800 seconds
0
0 to 1800 seconds
0
0 to 1800 seconds
0
50 or 60 Hz
As ordered
120 to 600 volts
As ordered
97% to 50% of NOMV
80% of NOMV in volts
97% to 50% of NOMV
80% of NOMV in volts
99% to (1UVD + 2%)
90% of NOMV in volts
99% to (2UVD + 2%)
90% of NOMV in volts
105% to 120%
115% of NOMV in volts
105% to 120%
115% of NOMV in volts
(1OVD - 2%) to 103%
110% of NOMV in volts
(2OVD - 2%) to 103%
110% of NOMV in volts
90% to 97% of NOMF
90% to 97% of NOMF
(1UFD + 1Hz) to 99%
(2UFD + 1Hz) to 99%
103% to 110% of NOMF
103% to 110% of NOMF
(1OFD - 1Hz) to 101%
(2OFD - 1Hz) to 101%
0 to 120 seconds
0
0=Disable, 1=Enable
0
10% to 30% of NOMV
10%
0=None, 1-Src1, 2=Src2
1
0=Disable, 1=Enable
0
0=Disable, 1=Enable
0
1 to 7 (1=Sunday)
12am to 11pm
00 to 59
0=Automatic, 1=Manual
0
0=Not, 1=Commit
0=No Load, 1=Load,
0
2=Disable
1 minute to 10 hours
1
0 to 120 seconds
0
0=Dual Utility,
1
1=One (Source 2)
2=Dual Generator
1 or 3
As Ordered
0 to 120 seconds
0
2 (2:1) to 500 (500:1)
2
0 to 6 seconds
0
Page 5