Xiria Product Family
User manual 994.570 G01 06
User manual
Xiria Product Family
994.570 G01 06
Eaton Industries (Netherlands) B.V.
P.O. box 23, 7550 AA Hengelo, The Netherlands
tel:
+31 74 246 91 11
e-mail:
info.electric@eaton.com
internet:
www.eaton.eu/electrical
Service emergency
Eaton - Electrical Solutions & Services :
tel: +31 74 246 68 88

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the xiria series and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton xiria series

  • Page 1 994.570 G01 06 Eaton Industries (Netherlands) B.V. P.O. box 23, 7550 AA Hengelo, The Netherlands tel: +31 74 246 91 11 e-mail: info.electric@eaton.com internet: www.eaton.eu/electrical Service emergency Eaton - Electrical Solutions & Services : tel: +31 74 246 68 88...
  • Page 2 Administrative data Issue number: G01 06 Date of issue: 12-11-2013 Translation of: Checked by Job title: Product Manager Name: A.R.A. Pikkert / B. ter Hedde Date: Initials: 994.570 G01 06...
  • Page 3: Table Of Contents

    Xiria CONTENTS GENERAL ....................5 Explanation of used warnings ................5 Safety relating to medium-voltage installations ..........5 Tools, aids and protection equipment ..............5 Product standards and guidelines used .............. 6 Product information ....................6 XIRIA SYSTEM DESCRIPTION ............10 Xiria System description..................
  • Page 4 Xiria Signals ......................... 29 4.4.1 Voltage detectors ....................29 4.4.2 Overcurrent indicator..................... 29 4.4.3 Trip indicator ......................29 Short-form instructions ..................30 REMOTE SIGNALLING AND REMOTE CONTROL ......31 Connection ......................31 Remote signalling (option) ................. 31 Remote control ....................31 5.3.1 24 V DC Remote tripping (option) ................
  • Page 5: General

    Operations involving the repair of the switchgear unit are to switching off; be carried out by or under the responsibility of Eaton. complete isolation; Information with respect to these operations is, therefore, protection from reactivation;...
  • Page 6: Product Standards And Guidelines Used

    (see Figure 1-1 to Figure 1-6). The panel type plate includes:  switch type;  technical specifications;  serial number and year of manufacture. Eaton Industries (Netherlands) BV Medium Voltage P.O. box 23, 7550 AA Hengelo, The Netherlands M.V. SWITCHGEAR IEC 62271-200 system: XIRIA r2.9...
  • Page 7 Xiria CURRENT TRANSFORMER IEC 61869-2 CURRENT TRANSFORMER IEC 61869-2 type: CTB 90 Make: EATON type: WIC1-W3H1 Make: ELEQ 75/5 A L1-L2-L3 S1 – S2 L1 – L2 – L3 28,8/0,075 A 5 VA Cl. 0,2 ext. 120% 0.1 VA Cl. 5P80 L1 –...
  • Page 8 Xiria Busbar system: Rated normal current ----------------------630----------------------------------- Rated short-time withstand current kA-s 20-1 20-1 20-1 20-1 20-1 Rated short time withstand current alternative kA-s 20-3 20-3 20-3 20-3 20-3 Rated peak withstand current Circuit-breakers: Rated normal current ---------------------200/500/630------------------------- Rated breaking current Rated short-circuit making current Rated Capacitive Switching Current Class ----------------------C2-------------------------------------...
  • Page 9 Xiria Table 2: Explanation oftype plate data in accordance with IEC Variable Description Unit system Release IEC reference type Type switching device serial no. Serial number year of man. Year of manufacturing w.o.no. Works order number Rated frequency Rated mainly active load breaking current Rated distribution line closed-loop breaking current Rated cable-charging breaking current Rated earth-faulth breaking current...
  • Page 10: Xiria System Description

    Xiria 2. XIRIA SYSTEM DESCRIPTION 2.1 Xiria System description The Xiria switchgear panels are available for applications up to 24kV. The system is fully metal enclosed and a highly compact and safe unit is achieved using high-quality internal insulation. All live primary components of the unit and the main components of the drive mechanisms are housed in a fully sealed enclosure.
  • Page 11: Cross-Section, Single Line Diagram And List Of Functions

    Xiria 2.2 Cross-section, single line diagram and list of functions Cable connected to the busbar Cable connected to earth Figure 2-1: Panel cross-sections and single line diagrams 1. Viewing window 2. Earth contact change-over switch 3. Busbar contact change-over switch 4.
  • Page 12: Technical Specifications, General

    Xiria 2.3 Technical specifications, general Item Explanation Specification Weight of the heaviest Nett (kg) Gross (kg) See delivery note for the transport unit exact value 1 panel 2 panels 2 panels with plinth 3 panels 3 panels with plinth 4 panels 4 panels with plinth 5 panels 5 panels with plinth...
  • Page 13: Installing The Unit

     vibrations during transport; taken in consultation with Eaton.  damage to the pressure relief valves. If the unit is Care should be taken not to damage the unit, even if the shipped by air, it should be carried in a cargo bay in packaging has not been removed.
  • Page 14: Lifting

    Xiria 3.2.1 Lifting ARNING The person in charge of lifting the Xiria unit must hold a certificate issued by the relevant authorities to certify that he/she is authorised to carry out these operations. After installation the lifting equipment (1) must not be removed.
  • Page 15: Preparation Prior To Installation

    Xiria 3.2.3 Preparation prior to installation The location of the unit is required to meet the conditions stated in par. 3.1.2. Remove the packaging and check the contents. Remove the doors of the left- and right-hand panels, see Figure 3-4. The door can only be removed if the panel is in the 'Cable earthed' position.
  • Page 16: Setting Up The Unit

    Xiria The following rules apply to a set-up with an arc channel: 3.2.4 Setting up the unit  The channel is to be connected to a location where no The Xiria system has been designed in accordance with danger can occur to personnel. the recommendations set out in IEC 62271-200 which ...
  • Page 17: Cable Assembly Instructions

    Xiria Table 4: Short-circuit capacity in relation to cable cones used Cone type I [A] Maximum Plug type Cable type EN 50181 short-circuit current Load-break 3.6-24kV 20kA-3s bolted T-plug Cu/Al XLPE switch Cu/Al XLPE Circuit- 3.6-24kV 20kA-0,4s plug type Cu/Al XLPE breaker L plug Cu/Al XLPE...
  • Page 18 Xiria Assembly steps if current transformers are installed around the primary cable The same steps should be followed as described at the standard assembly. For easy connection of the primary cables the current transformers in the cable compartment can be removed and remounted. For this the following steps should be taken: Open the cable compartment according to the standard instructions.
  • Page 19: Replacing The Cable Connection Cone

    A different type of cone can also be fitted in the circuit-breaker panel at a later stage. Two types are available, A and C in accordance with EN 50181. Contact Eaton for further details. 3.3.4 Applying test current and test voltage...
  • Page 20: Connection Of Station Earthing

    Xiria 3.4 Connection of station earthing The Xiria unit can be connected either to the left or to the right of the station earthing. An earth bar, to which the earth screens of the power cables and the system earth can be connected, is located at the rear of every cable connection compartment.
  • Page 21 Xiria Procedure (Xiria E with top-unit) Open top-unit with key. The secondary compartment is now accessible, see Figure 3-15. Figure 3-15 Procedure (Xiria Metering panel) Open integrated low voltage compartment, see Figure 3-16. The secondary compartment is now accessible. Figure 3-16 994.570 G01 06...
  • Page 22: Operation

    Xiria 4. OPERATION 4.1 Details of control panel The Xiria unit is equipped with two types of control panel, Figure 4-1 provides a summary of the control units on one for the load-break switch panel and one for the circuit- the control panels.
  • Page 23 Xiria Remove the handle and check that the position indicator (9) of the change-over switch indicates the busbar position. Turn the selector anti-clockwise until the switch control point (5) is revealed. Place the operating handle with the arrow pointing up in the switch control point (5).
  • Page 24: Switch Cable Earthing On/Off

    Xiria Initial position: 4.2.2 Switch cable earthing on/off In the neutral position (see Figure 4-5): In the operating position, the cable is connected to the  the switch is OFF, see switch (4) position indicator; main busbar of the unit; the switch is ON and the change- ...
  • Page 25: Gaining Access To Cable

    Should this be the case contact Eaton. Ensure by other means that the cable is dead before carrying out any further switching operations.
  • Page 26 Xiria Procedure Switch on the integrated cable earthing in accordance with the instructions in section 4.2.2. To open the cable connection compartment:  check, using the single line diagram and position indicators, whether the cable on the panel to be opened is earthed;...
  • Page 27: Interlocks

    Put the hasp of the padlock (D) through the hole on • Notify Eaton-ESS if the action is permissible the right (Figure 4-13 D). according to the switching tables but cannot be The hasp diameter can be 1-12 mm.
  • Page 28: Interlock For Circuit-Breaker/Load-Break Switch Opening Button

    Xiria 4.3.3 Interlock for circuit-breaker/load-break switch opening button The interlock on the opening button is to prevent the switch from being unintentionally opened. Once this interlock is in place, the flap in front of the opening button can no longer be lifted.
  • Page 29: Signals

    Xiria 4.4 Signals The Xiria unit features voltage detectors on the cable side and can be fitted with overcurrent indicators and trip indicators as options. 4.4.1 Voltage detectors The Xiria unit features voltage detectors in the control panel (12) conform IEC 61243-5 with LRM interface. The voltage detector includes an LCD screen with indication arrows and dots, one for each phase, see Figure 4-17.
  • Page 30: Short-Form Instructions

    Xiria 4.5 Short-form instructions In these short-form instructions the following procedures are described:  From closed service position to closed and locked earthed position.  From closed and locked earthed position to closed service position. Figure 4-20: Short-form instructions 994.570 G01 06...
  • Page 31: Remote Signalling And Remote Control

    Xiria 5. REMOTE SIGNALLING AND REMOTE CONTROL For correct connection and operating voltages see the circuit diagrams delivered with the unit. Remote signalling and electric remote control are available as options for Xiria switchgear units. Remote control is suitable for a maximum switching frequency of once a minute.
  • Page 32: Dc Remote Closing (Option)

    Xiria 5.3.2 24 V DC Remote closing (option) The panels concerned are provided with:  auxiliary contacts as described under remote signalling;  a controller;  a trip coil;  a closing motor;  a closing pushbutton on the frontside of the panel. If the supply voltage <...
  • Page 33: Inspection And Maintenance

    4.2.3. Clean the compartment with a dry cloth. down the unit and inform Eaton-ESS. Check the cable plug connection according to the plug supplier's instructions. Ensure that the cable does not impart any mechanical strain on the plug.
  • Page 34: Inspection Of The Moisture Absorbing Agent

    6.3.1 Material processing after dismantling Eaton pays a great deal of attention to the environmentally- 6.2.4 Testing voltage detection friendly design aspects of its units and installations. Eaton...
  • Page 35: Accessories And Options

    Xiria 7. ACCESSORIES AND OPTIONS 7.1 Supplied accessories Accessories 668251 Operating handle 135 mm for ON-OFF switching of the circuit-breaker and the load break switch and for busbar-earth position selection of the change- over switch. 668270 Operating handle 510 mm needed for operation of a Xiria unit inside a compact transformer station with limited access in the front area.
  • Page 36 Xiria Options 665417 Scissor type interlock, used in combination with a padlock inserted in the access hole for the vacuum Interrupter. It prevents switching ON and it prevents the operation of the change-over switch. 107926 Padlock, used in combination with the scissor type interlock and for padlocking the earth interlock on the front.
  • Page 37 Xiria Options E6042323 Short circuit indicator type SIGMA. It detects short-circuit currents in medium-voltage distribution networks. It consists of a display unit accommodated in a plug-in housing for panel mounting and three current transformers for short circuit sensing. 668002 Short circuit indicator type ALPHA-M. It detects short-circuit currents in medium-voltage distribution networks.
  • Page 38 Xiria Options E569882 Protection relay make Woodward SEG type WIC1-2PE Setting via DIP switches on the front. E569884 Protection relay make Woodward SEG type WIC1-3PE Setting via HEX switches on the front. E6056904 Protection relay make Woodward SEG type WIB1-2PE Setting via DIP switches on the front.
  • Page 39: Appendix 1 - Floor Plans

    Xiria APPENDIX 1 – FLOOR PLANS 994.570 G01 06...
  • Page 40 Xiria 994.570 G01 06...
  • Page 41 Xiria 994.570 G01 06...
  • Page 42 Xiria 994.570 G01 06...
  • Page 43 Xiria 994.570 G01 06...
  • Page 44 Xiria 994.570 G01 06...
  • Page 45: Appendix 2 - Voltage Detecting System (Wega)

    Xiria APPENDIX 2 – VOLTAGE DETECTING SYSTEM (WEGA) 994.570 G01 06...
  • Page 46 Xiria 994.570 G01 06...
  • Page 47 Xiria 994.570 G01 06...
  • Page 48: Appendix 3 - Orion 3.0

    Xiria APPENDIX 3 – ORION 3.0 994.570 G01 06...
  • Page 49: Appendix 4 - Short Circuit Indicator

    Xiria APPENDIX 4 – SHORT CIRCUIT INDICATOR 994.570 G01 06...
  • Page 50: Appendix 5 - Tariff Metering 12Kv

    Xiria APPENDIX 5 – TARIFF METERING 12KV A5.1 The system A5.1 Standard system description The Xiria system with tariff metering type MA consists of a three- or four panel switchboard with a circuit-breaker in the right panel. This circuit-breaker is provided with built-in cable side current- and voltage transformers for tariff metering.
  • Page 51 Xiria A5.1.3 Design specification of a switchboard with tariff metering with cable side current- and voltage transformers in the right panel: Choke coil and resistor for the anti- ferro resonance filter (L20-R20) Current transformers for metering phase L1, L2 and L3 (T1-T2-T3) Current transformers for protection phase L1, L2 and L3 (T4-T5-T6)
  • Page 52 Xiria transformers are made with earth screened connectors Voltage transformers: type A. The connections on the cable cones of the circuit- The voltage transformers are mounted inside the breaker (panel 3) are made with earth screened switchgear at the rear. They are connected with connectors type C, mounted in parallel with the preassembled internal primary cables to the circuit- connectors for the primary cables.
  • Page 53 Xiria A5.1.4 Connection of the primary main cables and the voltage transformers: Due to the limited mounting space inside the cable compartment the primary cables and the voltage transformers are connected with connectors make Tyco type RSTI 58. The connectors and cables for the voltage transformers are pretested and preassembled on the cable cones of the circuit-breaker.
  • Page 54 Xiria to the front and the secondary components can be A5.1.6 Allocation of the secondary connections for accesssed. The wiring for the connection of external metering: metering equipment can be connected through the holes in The switchboard is provided with a secondary front both side posts (B).
  • Page 55 Xiria 994.570 G01 06...
  • Page 56 Xiria 994.570 G01 06...