Mechanical Installation
1.3 Installation Conditions
To avoid overheating, the device must be ventilated. The recommended mini-
mum top and bottom distance between frequency converter and adjacent items
(may prevent air flow)are shown as figure below:
Fig. 1-1: Frequency converter mounting
VFC 3210 must be vertically installed on the metal wall.
●
Without heat dissipation holes on both sides of the housing, VFC
●
3210 can be installed side by side.
If one frequency converter is arranged above another, make sure
●
the air temperature into the inlet can not exceed 40℃.
An air guide is recommended between the frequency converters
●
to prevent the rising hot air being drawn into the upper frequency
converter if the upper limit of air temperature is exceeded.
Bosch Rexroth AG R912007861_Edition 02
Rexroth Frequency Converter VFC 3210