Commissioning
7.1
Measures prior to commissioning
Before commissioning the system, check that it is properly installed and connected. The
drive system must be commissioned as described in the operating instructions for the
converter/inverter.
Risk of electric shock
When commissioning/operating electric motors, parts of the motor are always at a
dangerous voltage. If this motor is not correctly handled/operated, this can result in death or
severe personal injury as well as significant material damage. All of the warning information
on the product must be carefully observed!
Danger from rotating rotor.
Provide the appropriate guards and covers for transmission elements.
Note
This list below does not claim to be complete. It may be necessary to perform additional
checks and tests in accordance with the specific situation at the plant or system.
Mechanical connection
Make sure that:
● Touch protection measures are in place for moving and live parts.
● The fitted keys in the shaft extension (if available) must be firmly secured to prevent them
● The motor has been correctly installed and aligned.
● The rotor can turn without coming into contact with other parts and components.
● The operating conditions correspond to the data specified on the rating plate.
Synchronous Motors 1FK7
Operating Instructions, 03/2011, 610.40700.40c
DANGER
WARNING
from being flung out.
7
37