Advanced Energy LumaSense Technologies E2T QUASAR Series Operation Manual page 40

Flare monitors
Table of Contents

Advertisement

2. Verify that the instrument's red "Flame-out" alarm LED is on and that the green LED is
off. If this is not the case, go to step 3 below.
3. Adjust the System Gain no more than 2 turns counter-clockwise so that the analog meter
reads .35. Once adjusted, the red "Flame Out Alarm" LED should light after the expected
delay. If this does not occur, proceed to step 5 below.
4. Verify that the analog meter reads at least .8 when the Flare is present. The procedure is
complete. (Do not proceed to step 5.)
5. Adjust the set-point pot (Figure 11, Item 10) to be above the unacceptable condition
observed in step 4 by .2 divisions on the meter.
a. Move the Gain/Setpoint Switch (Item 6) to the Setpoint position.
b. Adjust the setpoint as required; verify the Alarm LED lights.
c.
Return the Gain/Setpoint switch to the Gain position.
d. Return to step 4 above.
E
T QUASAR Flare Monitors Operation Manual
2
Operating the M8100FM-EXP • 40