Micro800™ 4 Ch Universal Analog Input Module
Environmental Tests
Radiated Emissions
Conducted Emissions
ESD immunity
(Performance Criteria B)
Radiated RF immunity
(Performance Criteria A)
EFT/B immunity
(Performance Criteria B)
Surge transient immunity
(Performance Criteria B)
Conducted RF immunity
(Performance Criteria A)
Publication 0100189-04 Rev. C
Industry Standards
CSIPR 11; Group 1, Class A
Rockwell Document QTP#X0327
IEC 61000-6-4:2007
Rockwell Document QTP#X0327
IEC 61000-4-2
Rockwell Document QTP#X0327
IEC 61000-4-3: Level 3
Rockwell Document QTP#X0327
IEC 61000-4-4*
Rockwell Document QTP#X0327
IEC 61000-4-5
Rockwell Document QTP#X0327
IEC 61000-4-6
Rockwell Document QTP#X0327
15
Test Level Limits
(Enclosure) Class A, 30 MHz – 1
GHz
Group 1, Class A (AC Mains), 150
kHz – 30 MHz
6 kV Indirect (Coupling Plate)
6 kV Contact Discharge (to points
of initial contact)
8 kV Air Discharge (to points of
initial contact)
10 V/M with 1 kHz sine-wave 80%
AM from 80...2000 MHz
10 V/M with 200 Hz sine-wave
50% Pulse 100% AM @900 MHz
10 V/M with 200 Hz sine-wave
50% Pulse 100% AM @1890 MHz
1 V/M with 1 kHz sine-wave 80%
AM from 2000...2700 MHz
(3 V/M goal)
Signal Ports:
± 3 kV @ 5 kHz for 5 minutes,
Criteria B (Marine?)
± 2 kV @ 5 kHz for 5 minutes,
Criteria A (Marine?)
± 2 kV @ 5 kHz for 5 minutes,
Criteria B (standard)
Power Ports:
± 2 kV @ 5 kHz for 5 minutes,
Criteria A (Marine?)
± 2 kV @ 5 kHz for 5 minutes,
Criteria B (standard)
Signal Ports:
± 2 kV line-earth {CM}@ 2Ω on
shielded ports
Power Ports
± 2 kV CM @ 12 Ω
± 1 kV DM @ 2 Ω
10 V rms with 1 kHz sine wave
80% AM from 150 kHz...80 MHz
on signal and power ports
Need help?