ABB SensyMaster FMT230 Commissioning Instruction page 47

Thermal mass flowmeter
Hide thumbs Also See for SensyMaster FMT230:
Table of Contents

Advertisement

FMT230, FMT250 THERMAL MASS FLOWMETER | CI/FMT230/250-EN REV. B
Changing an unknown Modbus slave ID
The Modbus Slave ID (address) of the device must be known for
Modbus communication.
Upon delivery, the Modbus Slave ID corresponds to the last two
digits of the serial number of the device (see Figure 34, item
If the Modbus address is not known, the Modbus Slave ID can be
reset via a Modbus broadcast message. To do this, the following
three Modbus registers must be sent to the bus together with
the function code 16 (0x10) 'Write Multiple Registers.'
To set the Modbus Slave ID the Sensor ID of the device from the
calibration certificate will be needed.
Figure 35: Sensor ID on the calibration certificate
Address / data type
[register length]
65521 TUSIGN32 [2]
2
).
65523 TUSIGN32 [2]
65525 TUSIGN32 [2]
The three Modbus registers must now be sent from the Modbus
master to the broadcast address '0.' All of the devices connected
to the bus receive the message, but only the device addressed
via the manufacturer code and the Sensor ID sets the Modbus
Slave ID to the new required value.
1 Functional code 16
2 Broadcast address "0"
3 Register start address
4 Number of registers
Figure 36: Write Multiple Registers (example)
Description
manufacturerDeviceID
The manufacturer code (ABB = 0x1A) and the
device code (FMT = 0x27) must be written to
register 65522.
sensorSerialID
The Sensor ID of the device (on the calibration
certificate). The information must first be written
in the high-byte (65524) of the register.
slaveID
The new Modbus Slave ID must be written in the
high byte (65526) of the register.
5 Manufacturer and device codes
6 Sensor ID
7 New Modbus Slave ID
47