The package of the TLE Scalable Series 40 - 150
includes the "Anti-Humidity & Corrosion devices"
against the formation of humidity and corrosion
during the transportation and the storage of the UPS.
"Anti-Humidity & Corrosion devices" components:
A. Humidity indicator
B. Desiccant bag (2 pcs.)
C. VCI foil base
D. PE stretch foil
WARNING !
It's MANDATORY TO REMOVE the "Anti-Humidity & Corrosion devices" during
the unpacking of the UPS!
Humidity indicator
Before removing the devices "C - VCI foil base" & "D - PE stretch foil", check
the status of the "A - Humidity indicator".
10% to 70%:
The UPS can be commissioned.
80%:
The UPS shall not be commissioned. Please contact your "GE Service Center".
PROTECTIVE FOIL
to remove as indicated
in the label
Fig. 4.6-4 Location of the "Protective Foil"
Modifications reserved
GE_UPS_ISG_TLE_SUL_40K_M15_1US_V010.docx
Critical Power
ANTI-HUMIDITY & CORROSION DEVICES
PROTECTIVE FOIL
TLE Scalable Series 40 - 150 is provided with a
"Protective Foil", on the roof and door/front panels, to
prevent material from falling into UPS.
PROTECTIVE FOIL
to remove as indicated
in the label
XA
B
A
Q1
B
C
Fig. 4.6-3 Location of the "Anti-Humidity & Corrosion devices"
WARNING !
It's MANDATORY TO REMOVE the
"Protective Foil" but only just before
the first start-up of the UPS as
indicated in the appropriate label!
The removal of the "PROTECTIVE
FOIL" should be performed only by a
GE FIELD SERVICE ENGINEER!
Installation Guide TLE Scalable Series 40 - 150 UL S1
D
A
HUMIDITY
INDICATOR
80
%
70
%
60
%
50
%
40
%
30
%
20
%
B
DESICCANT
Page 21/53