Final units, first and last, of a RPA Parallel System
On the two boards P13/P14 – IM0022 – Bus Interface Board, of the first and last units of a Parallel
System, the switches SW1-1/2/3/4/5/6 MUST BE IN POSITION ON (see Fig. 4.9.2-2).
Intermediate units of a RPA Parallel System
On the two boards P13/P14 – IM0022 – Bus Interface Board, of the intermediate units of a Parallel
System, the switches SW1-1/2/3/4/5/6 MUST BE IN POSITION OFF (see Fig. 4.9.2-3).