Size of Branch Circuit Over Current Protection - All Models: - "CAUTION - To reduce the risk of fire,
only connect UPS to a circuit provided with (see below) maximum amperes branch circuit over
current protection in accordance with the NEC (National Electric Code), NSI / NFPA 70
UPS rating
TLE Scalable Series 150/40
TLE Scalable Series 150/50
TLE Scalable Series 150/80
TLE Scalable Series 150/100
TLE Scalable Series 150/120
TLE Scalable Series 150/150
UPS rating
TLE Scalable Series 150/40
TLE Scalable Series 150/50
TLE Scalable Series 150/80
TLE Scalable Series 150/100 1x AWG 4/0
TLE Scalable Series 150/120 2x AWG 2/0
TLE Scalable Series 150/150 2x AWG 3/0
Modifications reserved
GE_UPS_ISG_TLE_SUL_40K_M15_1US_V010.docx
Critical Power
F31
AC Input Rectifier
80 A
90 A
175 A
175 A
225 A
300 A
WIRING
Wire sizing according to:
NEC Section 210-20 (A)
Use 194°F (90°C) copper.
Wiring requirements:
AC INPUT RECTIFIER:
AC INPUT BYPASS:
AC OUTPUT:
DC INPUT:
Maximum recommended cable size
Rectifier Input Bypass Input
1x AWG 2
1x AWG 4
1x AWG 1
1x AWG 1
1x AWG 4/0
1x AWG 4/0
1x AWG 4/0
2x AWG 1/0
2x AWG 3/0
F32
AC Input Bypass
AC Input
60 A
90 A
175 A
175 A
200 A
250 A
Table 310-16.
3-Phase, 4 wire plus Ground
3-Phase, 4 wire plus Ground
3-Phase, 4 wire plus Ground
2 wire (positive and negative) plus Ground
DC Input
1x AWG 1
1x AWG 1/0
1x AWG 4/0
2x AWG 2/0
2x AWG 3/0
2x AWG 4/0
Installation Guide TLE Scalable Series 40 - 150 UL S1
F33
F34
DC Input
80 A
110 A
90 A
125 A
175 A
200 A
175 A
250 A
225 A
300 A
300 A
400 A
AC Output
GND
1x AWG 4
AWG 6
1x AWG 1
AWG 6
1x AWG 3/0
AWG 4
1x AWG 4/0
AWG 4
2x AWG 1/0
AWG 4
2x AWG 3/0
AWG 3
Page 25/53