Technical Details - Pilz PSS Series Operating Manual

Programmable safety control
Hide thumbs Also See for PSS Series:
Table of Contents

Advertisement

Available languages

Available languages

Technical Details

Electrical Data
Supply Voltage
Tolerance Range
Galvanic Isolation
Polarity Protection
Connection Type
Inputs
Number of Inputs
Input Signals:
"1"-Signal (high)
"0"-Signal (low)
Input Current
Input Delay
E0 ... E15
E16 ... E31
Status Indicator
Environmental Data
Protection type (EN 60 529, 10/91)
Protection class (DIN VDE 0106,
Part 1/A1, 04/90)
Mounting position
Ambient temperature (DIN IEC 68-2-14, 06/87) 0 ... 60 °C
Storage temperature (EN 60 068-2-1/-2, 03/93) -25 ... +70 °C
Relative humidity
(DIN IEC 68-2-30, 09/86)
Vibration (EN 60 068-2-6, 04/95)
Shock (DIN IEC 68-2-29)
EMC
Mechanical Data
Weight PSS DI/PSS1 DI
The names of products, goods and technologies are trademarks of the companies concerned
Operating Manual
24 V DC
20 ... 30 V DC including residual ripple
Yes (Optocoupler)
Yes
Screw Connector, max. 2.5 mm
32
+15 ... +30 V DC
-3 ... +5 V DC
Average 6 mA
1 ms
3 ms
LED per input
IP 20 (installed on module rack)
1 (installed on module rack)
Vertical on module rack
Max. 95 % r.h.
Frequency range: 10 ... 100 Hz
Amplitude: 0.1 mm, max. 5g
30g, 11 ms/10g, 16 ms
EN 50 082-2, 03/95
EN 55 011 A, 08/96
840 g/450 g
2
(AWG 12)
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pss diPss1 di

Table of Contents